Connect Breeching
General chimney requirements:
•Designed for natural draft firing. Connect boiler to vertical chimney.
Insufficient draft can cause flue gas leakage and carbon
monoxide emissions, which will lead to severe personal injury or death.
•Use vent material approved by local codes for
—NFPA 31, Installation of
—NFPA 211, Standard for Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances.
—In Canada, refer to CSA B139, Installation Code for
•NFPA 211 requires chimney to be lined before connected to boiler.
Inspect existing chimney before installing new boiler. Failure to
do any of the following will result in severe personal injury or death:
—Clean chimney, including removal of blockage.
—Repair or replace damaged pipe or liner.
—Repair mortar and joints.
To prevent downdrafts, extend chimney at least 3 feet above highest point where it passes through roof and 2 feet higher than any portion of building within 10 feet. Increase chimney
•Minimum clearances from vent pipe to combustible material:
6 inches — Type “L” doublewall vent
18 inches — Singlewall vent
•Minimum chimney sizes should be used.
Oversized chimneys, outside masonry chimneys and/or
derated inputs can result in condensation in chimney.
Connect breeching:
Long horizontal breechings, excessive number of tees and
MINIMUM CHIMNEY SIZE TABLE
|
|
|
|
|
|
|
|
| MINIMUM |
|
|
|
| |
|
|
| * * * |
|
|
|
| |||||||
|
|
|
|
| MINIMUM |
|
|
| I=B=R |
|
|
|
| |
|
| BOILER |
| |||||||||||
|
|
|
|
|
|
|
|
| MINIMUM |
| ||||
|
| MODEL |
|
| BREECHING |
|
|
| CHIMNEY SIZE |
|
| CHIMNEY |
| |
|
|
|
|
|
|
|
|
|
| |||||
|
| NUMBER |
|
| DIAMETER |
|
|
| RECT. | ROUND |
|
| HEIGHT |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
| 5" |
|
| 8" x 8" | 6" |
| 15' |
| ||||
|
|
| 6" |
| * |
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| 6" |
|
| 8" x 8" | 7" |
| 15' |
| ||||
|
|
|
|
|
|
|
|
|
| |||||
|
|
| 7" |
|
| |||||||||
|
|
|
|
| * |
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 7" |
|
| 8" x 12" | 7" |
| 20' |
| ||||
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
| * * |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*6¾" x 6¾" inside liner
** 6½" x 10½" inside liner
** * Flue collar on boiler is 7" diameter
elbows, or other obstructions restricting combustion gas flow can result in possibility of condensation, flue gas leakage and carbon monoxide emissions, which can lead to severe personal injury or death.
1.Install 2 flue pipe brackets.
2.Connect
—Back outlet — see FIGURE 7.
—Top outlet — see FIGURE 8.
3.Connection must be made above bottom of chimney to avoid blockage. Breeching must not enter chimney far enough to cause obstruction. Use thimble or slip joint where breeching enters chimney to allow removal for cleaning.
4.When burner and boiler are properly installed, draft overfire will be approximately
to
5.An induced draft fan for the chimney may be necessary if:
—Excessive resistance to flow of combustion gases can be expected.
—
—Chimney height is less than recommended. Seal all vent joints. Interlock burner with
fan operation.
12