Appendix

Burner adjustments for “P” and “A” boilers:

Final burner adjustments must be made using combustion test

equipment to assure proper operation. Do not fire boiler without water or sections will overheat.

1.Refer to burner manual for start-up.

2.Allow boiler to heat to design condition.

3.Using combustion test equipment, adjust burner for:

a.CO2 between 11% and 12% and 0 smoke.

b.-0.01" to -0.02" W.C. draft in combustion chamber.

To connect SGO boilers to indirect-fired water heaters:

Install and wire per water heater manual provided with water heater.

If boiler already has a tankless heater installed:

Remove tankless heater and install cover plate.

OR

Leave tankless heater installed. Drain coil and remove piping. Do not plug holes in tankless heater front plate.

27

Page 27
Image 27
Weil-McLain 550-141-829/1201 manual Appendix, Burner adjustments for P and a boilers