3
Install water piping (continued)
Chilled water systems | Figure 10 Chilled water system plus optional | |
1. Install boiler so that chilled medium is piped in parallel with the heating | DHW piping | |
| ||
boiler. Use appropriate valves to prevent chilled medium from entering |
| |
boiler. See Figure 10 for typical installation of balancing valve and check |
| |
valve. |
| |
2. The space heating system may be zoned with circulators if a separate |
| |
circulator is supplied for the chilled water loop. |
| |
3. If boiler is connected to heating coils located in air handling units where |
| |
they can be exposed to refrigerated air, use flow control valves or other |
| |
automatic means to prevent gravity circulation during cooling cycle. |
| |
| Follow these piping guidelines below to ensure chilled water |
|
|
| |
| does not enter the boiler loop. |
|
|
| |
| Chilled medium, if used, is piped in parallel with heating boiler |
|
|
| |
| as shown in Figure 10. Use appropriate valves to prevent chilled |
|
| medium from entering boiler. |
|
| If boiler is connected to heating coils located in air handling |
|
| units where they can be exposed to refrigerated air, use flow |
|
| control valves or other automatic means to prevent gravity |
|
| circulation during cooling cycle. |
|
NOTE 1: To ensure adequate flow rate through the boiler, use the following |
| |
pipe size on all boiler loop piping (connecting boiler to and from |
| |
the primary/secondary connection, item 21): |
| |
| ||
| ||
| ||
| Use at least the minimum piping size above and pipe the boiler |
|
|
| |
| using only primary/secondary piping as shown. Failure to |
|
|
| |
| follow these guidelines could result in system problems. |
|
Legend | Figure 10 |
|
| |
1 | Ultra boiler |
| 12 | Boiler circulator |
2 | Indirect water heater (DHW), if used | 13 | Zone valves, typical | |
3 | Boiler relief valve (see page 12 for piping details) | 15 | ||
4 | Relief valve discharge piping (see page 12 for details) | 16 | Water chiller | |
5 | DHW circulator (see page 14 for suggested sizing) | 17 | Check valve | |
6 | Isolation valves | 18 | Strainer | |
7 | System circulator | 19 | Balancing valve | |
9 | Air separator (DO NOT use automatic air vents on systems fitted with closed- | 20 | ||
| type tanks) | 21 | Primary/secondary connection | |
|
|
|
10Flow/check valves (with weighted seats to prevent gravity circulation)
11Purge/drain valves
18 | Part number |