Maintenance — general
Replace boiler jacket front door after startup or servicing
Replace boiler jacket front door after start or servicing. The boiler front door must be securely fastened to the boiler to prevent boiler from drawing air from inside the boiler room. This is particularly important if the boiler is located in the same room as other appliances. Failure to keep the door securely fastened could result in severe personal injury or death.
General maintenance
1.Oil motor in system requiring regular oiling.
2.See Oil bearing circulators for motor oiling procedures.
Oiled bearing circulators
1.The circulator shipped with the Ultra boiler is water- lubricated. No oiling is required.
2.Check other circulators in the system. Oil any circulators requiring oil, following circulator manufacturer’s instructions.
Cleaning boiler heat exchanger
The boiler contains ceramic fiber materials. Use care when handling these materials per instructions on page 29 of this manual. Failure to comply could result in severe personal injury.
1.Shut down boiler:
a.Follow “To Turn Off Gas to Appliance” instructions on boiler and Lighting instructions.
b.Do not drain boiler unless it will be exposed to freezing temperatures. If using freeze prevention fluid in system, do not drain.
2.Allow time for boiler to cool to room temperature if it has been firing.
3.Remove jacket front door by removing two knurled head screws at lower front. Lift door away from boiler to remove.
4.Follow procedure below to access the heat exchanger interior.
Access exchanger: Ultra-80 and Ultra-105 Only
1.Remove (4)
2.Remove the air silencer by separating it from the air adapter on the blower inlet.
3.Disconnect the gas valve plug, blower power supply plug and blower control connector.
4.Release the exchanger cover plate by removing the nuts securing it to the exchanger.
5.Pull the entire blower/venturi/gas valve/cover plate assembly out of the boiler. (See pages 39 or 41 for component identification and locations.)
6.Use a vacuum cleaner to remove any accumulation on the heating surfaces. Do not use any solvent.
7.If the vacuum cleaner is unable to clean completely, wash the heating surfaces with clean, warm water. If necessary, use a piece of
8.Inspect the heat exchanger cover plate insulation. Replace if insulation is damaged. Read the ceramic fiber WARNING on page 29 before handling or disposing of ceramic fiber materials.
9.
10.Connect gas valve electrical plug and blower power and control connectors.
Inspect the
11.Secure gas valve inlet adapter to gas valve with (4)
12.
13.Install access cover gasket, chamber insulation assembly and cover. Secure cover with nuts.
14.See continued instructions on next page.
Part number | 33 |