GOLD CGa
3c Water piping — multiple zones
Piping multiple zones
Follow instructions on pages 16 and 17 to install near- boiler or
RADIANTIHEATINGTSYSTEMSTOR CONVERTEDEGRAVITY SYS
TEMS below, if applicable.)
See &IGURE or &IGURE PAGE TO COMPLETE IN- stallation.
Zoning with circulators (Figure 11) (return temp over 130°F)
1.Size each circulator to individual circuit require- ments.
$O NOTOINSTALLTCIRCULATOR ON BOILER EXCEPTCFOROPRI- mary/secondary piping).
3.Install isolation (balancing) valves to adjust flow to distribute heat to all zones.
4.Install and wire a separate relay for each zone cir- culator.
Zoning with zone valves (Figure 12) (return temp over 130°F)
1.Install isolation (balancing) valves to adjust flow to distribute heat to all zones.
2.Provide a separate
Piping for radiant heating systems or converted gravity systems
Converted gravity (or steam) systems
Whenever possible, use the primary/secondary piping shown in &IGURESU or on page 21. This piping de- sign allows changing boiler flow rate without affecting primary circuit flow rate.
If &IGURESU or cannot be used, use the
Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sec- tions or burners, resulting in severe personal injury, death or substantial property damage.
Radiant heating systems
Preferably, use primary/secondary piping, as shown in &IGURESU or on page 21. Alternatively, use the method of either &IGURE or &IGURE on page 23. $O NOTOUSESTHEHPIPING OF &IGURE
If radiant system tubing has no oxygen barrier, a HEAT EXCHANGER must be used.
Radiant heating system piping should include a means of regulating the boiler return water temperature and the system supply temperature (such as provided by an injection pumping
CONTROL R"OILER RETURN WATERTTEMPERATURERWILL BE ADEQUATELY CONTROLLED USINGITHEHMETHODSH shown in this manual provided the system supply temperature is relatively constant.
$/ ./4 apply the methods in this manual if the system is equipped with an OUTDOORDRESETS CONTROL. Instead, provide controls and piping which can regulate the boiler return water
TEMPERATURERAT NO LESS THAN ®ARDLESS OF SYSTEM SUPPLY TEMPERATUREA#ONTACTTYOUR