Weil-McLain CGA25SPDN GOLD CGa Gas-FiredWater Boiler - Boiler Manual, Does vent damper operate?

Models: CGA25SPDN

1 68
Download 68 pages 27.39 Kb
Page 56
Image 56
Does vent damper operate?

GOLD CGa Gas-Fired Water Boiler — Boiler Manual

11c Troubleshooting — spark-pilot boilers (continued)

CHART 4 Spark-ignited pilot DAMPER light flashing

— If POWER light is flashing: Usually indicates vent damper failed to prove open within 5 minutes —

— If POWER light is steady: Usually indicates vent damper closed during run cycle —

Electrical shock hazard — Wherever you see TURN OFF POWER , follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.

Reset boiler control by turning off power at service switch or turning down thermostat for at least 45 seconds.

Thermostat should call for heat and appropriate zone valves open. The TSTAT CIRC and LIMIT lights should come on.

Does vent damper operate?

No

• Wait 45 seconds.

Does vent damper operate?

Yes

No

Yes

 

 

 

Remove DAMPER plug (Figure 30, Item 6, page 53) from plug receptacle of control module.

Place voltmeter leads across the top two pins (1 and 4) of the DAMPER receptacle.

Does the voltmeter indicate 24 VAC?

No

Yes

 

 

 

• Try reseating plug in module receptacle and restart.

• If vent damper still does not work, replace vent damper assembly or actuator.

• Retest.

Are the TSTAT CIRC and LIMIT lights on steady?

Yes

 

No

 

 

 

 

 

Replace control

 

• Make sure thermostat is

 

calling for heat. If lights

 

module.

 

 

 

still don't come on, see

Retest.

 

 

Chart 7, page 59.

 

 

 

 

 

 

 

• Wait 5 minutes.

Is PRESS SWITCH light flashing?

No

 

Yes

 

 

 

 

 

• Boiler should be in

 

normal operating

 

sequence.

 

• Observe operation until

Does vent damper actuator

thermostat is satisfied.

indicator show damper is

 

open?

 

No

 

Yes

 

 

 

 

 

 

 

Remove damper wiring

 

 

 

 

plug at damper and firmly

Replace vent damper

 

 

reconnect.

 

assembly or actuator.

 

Recheck boiler operation.

Retest.

 

If problem persists,

 

 

 

 

replace vent damper

 

 

 

 

assembly or actuator.

 

 

 

 

 

56

Part Number 550-101-009/0107

Page 56
Image 56
Weil-McLain CGA25SPDN manual GOLD CGa Gas-FiredWater Boiler - Boiler Manual, Does vent damper operate?