Weil-McLain GL-E223-ADOC 0311 manual Domestic water piping requirements, Hot Water Can Scald

Models: GL-E223-ADOC 0311

1 44
Download 44 pages 33.55 Kb
Page 5
Image 5

AQUA PLUS indirect-fired water heaters — Product Manual

Pre-installation (continued)

Domestic water piping requirements

1.Install unions on all piping for easy removal of water heater.

2.Use dielectric unions or couplings to protect hot and cold water fittings from corrosion when connecting dissimilar materials such as copper and galvanized iron pipe.

3.When the supply pressure is higher than 70 PSIG, install a pressure reducing valve on cold water supply line to prevent water loss through T&P relief valve. A thermal expansion tank is also required.

4.If the water heater will replace a tankless coil in the boiler, discon- nect piping to coil or remove coil from boiler and replace with a cover plate. Allow water to drain from coil. Do not plug the tankless coil.

Plugging tankless coil inlet and outlet will result in severe personal injury, death or substantial property damage.

Studies have indicated that dangerous bacteria,

including legionella pneumophila, can form in

the potable water distribution system if certain minimum water temperatures are not maintained. Contact your local health department for more information.

Water heater operating restrictions

1. Read the operating limits under “Operating restrictions,” page 3.

Magnesium anode — The water heater is equipped with a magnesium sacrificial anode. The anode may erode over time, and should be inspected at least once annually, only by a qualified service technician. For installations with a likelihood of poor water conditions, the anode should be inspected at least every six months. Failure to comply could result in loss of protection by the anode, causing possible severe personal injury, death or substantial property damage due to water heater leakage.

The domestic water chloride concentration must not ex- ceed 200 ppm. High chloride concentrations can rapidly disintegrate the water heater’s protective anode.

Boiler water restrictions

1. Read the WARNINGS under “Boiler water restrictions,” page 3.

Hot Water Can Scald!

Water heated to temperature for clothes washing, dish washing and other sanitizing needs can scald and cause permanent injury.

Children, elderly, and infirm or physically handi- capped persons are more likely to be permanently injured by hot water. Never leave them unattended in bathtub or shower. Never allow small children to use a hot water tap or draw their own bath.

If anyone using hot water in the building fits the above description, or if state laws or local codes require certain water temperatures at hot water taps, you must take special precau- tions:

Use lowest possible temperature setting.

Install some type of tempering device, such as an automatic mixing valve, at hot water tap or water heater.Automatic mixing valve must be selected and installed according to valve manufacturer’s recommendations and instructions.

Water passing out of drain valves may be extremely hot. To avoid injury:

Make sure all connections are tight.

Direct water flow away from any person.

Protection must be taken against excessive tem- perature and pressure! — Installation of a tem- perature & pressure (T&P) relief valve (provided with water heater) and a thermostatic mixing valve (provided by installer) is required.

Part number GL-E223-ADOC 0311

5

Page 5
Image 5
Weil-McLain GL-E223-ADOC 0311 Domestic water piping requirements, Water heater operating restrictions, Hot Water Can Scald

GL-E223-ADOC 0311 specifications

The Weil-McLain GL-E223-ADOC 0311 is a notable addition to the lineup of high-efficiency cast iron boilers designed for both residential and commercial applications. This model stands out due to its focus on reliability, longevity, and energy efficiency, making it an ideal solution for those seeking effective heating solutions.

A key feature of the GL-E223 model is its durable cast iron construction. The cast iron heat exchanger not only enhances the boiler's overall resilience but also improves its thermal efficiency. This characteristic ensures the boiler can withstand the stress of continuous operation while providing consistent heating performance year after year.

The GL-E223-ADOC 0311 employs advanced burner technology, which optimizes combustion efficiency, reducing fuel consumption. With its ability to modulate based on the heating demand, the boiler adjusts its output to ensure it runs at peak efficiency, minimizing energy waste. This feature is particularly beneficial in terms of energy savings and reducing operational costs over time.

In terms of sizing, the Weil-McLain GL-E223 model is engineered to provide adequate heating for a wide range of applications. Its output capacity is meticulously designed to accommodate residential heating requirements while being robust enough for light commercial usage. The controls and monitoring systems integrated into this boiler allow for easy adjustments and improved system management.

One significant characteristic of this model is its built-in features for enhanced safety and convenience. The boiler includes safety controls that prevent overheating, as well as an easy-access inspection and cleaning configuration that extends the life of the unit and eases maintenance efforts.

Furthermore, the GL-E223-ADOC 0311 is designed to be compatible with a range of hydronic heating systems. This adaptability allows for seamless integration into existing infrastructure or new installations, allowing homeowners and businesses the potential for improved heating solutions without extensive modifications.

Overall, the Weil-McLain GL-E223-ADOC 0311 encompasses advanced engineering with its cast iron construction, efficient burner technology, and user-friendly features that ensure reliability and efficiency. Whether for new installations or upgrades, this boiler is a solid choice for efficient heating solutions, resonating well with those prioritizing energy conservation and long-term performance.