Domestic water piping (continued)

AQUA PLUS indirect-fired water heaters — Product Manual

Domestic water piping (continued)

LEGEND for Figure 2, page 6

Domestic water supplied to fixtures that could pose an injury hazard due to high temperature, such as showers and faucets, should be equipped with a temperature regulating device, such as an anti-scald mixing valve.

When the supply pressure is higher than 70 PSIG, install a pressure reducing valve on cold water supply line to prevent water loss through T&P relief valve. A thermal expansion tank is also required.

This symbol, where used in this manual, indicates the item is required by Massachusetts code.

Do not install any valve between T&P relief valve and tank connection, or on T&P relief valve discharge piping. Do not plug T&P relief valve or its discharge piping. Improper placement and piping of T&P re- lief valve can cause severe personal injury, death or substantial property damage.

11Temperature adjustment knob

12Anode access

The anode is specially made for this water heater. Use only the anode available from Weil-McLain, as listed in Replacement parts.

13Mixing valve — Manual backgroundRECOMMENDED

This symbol indicates the item is optional, unless required by applicable codes.

1Domestic cold water inlet connection — see Fig- ure 3, page 6 for size

2Domestic hot water outlet connection — see Fig- ure 3, page 6 for size

3Domestic recirculation connection — see Fig- ure 3, page 6 for size

4Boiler water inlet to coil — see Figure 3, page 6 for size

5Boiler water outlet from coil — see Figure 3, page 6 for size

6Drain valve — provided by installer

Install a drain valve on the DHW inlet to the water heater as shown.

7Piping from drain valve

Pipe from drain to floor drain, if available.

8 T&P valve connection

9T&P relief valve — supplied with water heater

Use only the T&P valve supplied with the water heater. See Replacement parts for part number.

Install the T&P relief valve in the top center tapping, as shown.

10T&P relief valve discharge piping —

must be made of material serviceable for temperatures of 250°F or greater.

must be directed so that hot water flows away from all persons.

must be directed to a suitable place for disposal.

must be installed so as to allow complete draining of the T&P relief valve and discharge line.

must NOT be excessively long — using more than 2 el- bows or 15 feet of piping can reduce discharge capacity.

must NOT be directly connected to a drain — terminate discharge piping within 6” from floor — refer to local codes.

must NOT be plugged, reduced or restricted.

must NOT be subjected to freezing.

Part number GL-E223-ADOC 0311

See Replacement parts for thermostatic mixing valves available from Weil-McLain.

14Domestic cold water supply

When the water supply pressure is higher than

70PSIG, install a pressure-reducing valve on the cold water supply line to prevent leakage from the T & P relief valve. A thermal expansion tank is also required.

15Domestic mixed-temperature water supply to system (when used — requires mixing valve)

16Domestic high-temperature hot water supply to system

17Heat trap loops (12” minimum) — Manual background

18Isolation valves

19Thermal expansion tank — Manual background

REQUIRED if cold water line is equipped with a backflow preventer or pressure reducing valve — see EXPANSION TANK WARNING on page 6.

20Shock arrester — Manual background

Dishwashers, clothes washers, and fast-closing positive shutoff valves incorporated in the system all contrib- ute to creating water shock. Install a water hammer arrester to prevent damage to pipes and appliances. See control manufacturer’s instructions for applica- tion and installation.

21Unions

Use dielectric unions or couplings to protect hot and cold water fittings from corrosion when connecting dissimilar materials such as copper and galvanized iron pipe.

22Backflow preventer — Manual backgroundManual background(required for Commonwealth of Massachusetts)

23Vacuum breaker — Manual background

24Pressure reducing valve — Manual background

REQUIRED when the supply pressure is higher than 70 PSIG — A thermal expansion tank is also required.

7