AQUA PLUS
Recirculation (continued)
Figure 4 Time lag to obtain hot water at fixture for branch lengths of 10 and 25 feet (ASPE Domestic Water Heating Design Manual)
Time in seconds required to get hot water at fixture (from ASPE)
Fixture flow rate (GPM) - |
|
| 0.5 |
| 1.5 |
| 2.5 |
| 4.0 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Piping length (feet) - |
| 10 |
| 25 | 10 |
| 25 | 10 |
| 25 | 10 |
| 25 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Copper pipe | ½” | 25 |
| 63 | 8 |
| 21 | 5 |
| 13 | 3 |
| 8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ¾” | 48 |
| 119 | 16 |
| 40 | 10 |
| 24 | 6 |
| 15 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Steel pipe | ½” | 63 |
| 157 | 21 |
| 52 | 13 |
| 31 | 8 |
| 20 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ¾” | 91 |
| 228 | 30 |
| 76 | 18 |
| 46 | 11 |
| 28 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CPVC pipe | ½” | 64 |
| 159 | 21 |
| 53 | 13 |
| 62 | 8 |
| 20 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ¾” | 95 |
| 238 | 32 |
| 79 | 19 |
| 48 | 12 |
| 30 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NOTE: Select branch size and length for less than 31 seconds delay.