Recirculation (continued)

AQUA PLUS indirect-fired water heaters — Product Manual

Recirculation (continued)

Figure 4 Time lag to obtain hot water at fixture for branch lengths of 10 and 25 feet (ASPE Domestic Water Heating Design Manual)

Time in seconds required to get hot water at fixture (from ASPE)

Fixture flow rate (GPM) -

 

 

0.5

 

1.5

 

2.5

 

4.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Piping length (feet) -

 

10

 

25

10

 

25

10

 

25

10

 

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Copper pipe

½”

25

 

63

8

 

21

5

 

13

3

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

¾”

48

 

119

16

 

40

10

 

24

6

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Steel pipe

½”

63

 

157

21

 

52

13

 

31

8

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

¾”

91

 

228

30

 

76

18

 

46

11

 

28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPVC pipe

½”

64

 

159

21

 

53

13

 

62

8

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

¾”

95

 

238

32

 

79

19

 

48

12

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Select branch size and length for less than 31 seconds delay.

Figure 5 Recirculation components