3. Quick Start

This Quick Start Guide describes a simplified installation procedure for the IPS-800-D20, IPS-800E-D20, IPS-1600-D20 or IPS-1600E-D20 hardware, which will allow you to communicate with the unit in order to demonstrate basic features and check for proper operation.

Note that this Quick Start Guide does not provide a detailed description of unit configuration or discuss advanced operating features. For more information, please refer to the Installation, Configuration and Operation sections in this User's Guide.

3.1.Hardware Installation

3.1.1.Apply Power to the IPS

Refer to power rating nameplate on the IPS back panel, and then connect the unit to an appropriate power source. Note that the IPS features two separate AC inputs and two separate power busses; connect the power cables (supplied with the unit) to the unit's Circuit "A" and Circuit "B" Power Inlets, install the cable keepers, then connect the cables to an appropriate power source. Refer to the table below for information concerning power requirements and maximum loads.

Model

Total

Input

Max. Load

Max. Load

Max. Load

Number

Outlets

Voltage

per Outlet

per Bus

per Unit

 

 

 

 

 

 

IPS-800-D20

8

100 to

15 Amps

20 Amps

40 Amps

 

 

120 VAC

 

 

 

IPS-800E-D20

8

100 to

15 Amps

20 Amps

40 Amps

 

 

240 VAC

 

 

 

 

 

 

 

 

 

IPS-1600-D20

16

100 to

15 Amps

20 Amps

40 Amps

 

 

120 VAC

 

 

 

IPS-1600E-D20

16

100 to

15 Amps

20 Amps

40 Amps

 

 

240 VAC

 

 

 

Set the Main Power Switch in the ON position; the ON LED should light, and the RDY LED should begin to flash.