Whirlpool 315420-000, W10100910 warranty Water System Piping, Piping Installation

Models: W10100910 315420-000

1 32
Download 32 pages 41.35 Kb
Page 12
Image 12

Water System Piping

Piping Installation

Piping, fittings, and valves should be installed according to the installation drawing (Figure 13). If the indoor installation area is subject to freezing temperatures, the water piping must be protected by insulation.

7.After piping has been properly connected to the water heater, remove the aerator at the nearest hot water faucet. Open the hot water faucet and allow the tank to completely fill with water. To purge the lines of any ex- cess air, keep the hot water faucet open for 3 minutes after a constant flow of water is obtained. Close the faucet and check all connections for leaks.

Water supply pressure should not exceed 80% of the working pressure of the water heater. The working pressure is stated on the water heater’s data plate. If this occurs,

a pressure limiting valve with a bypass may need to be installed in the cold water inlet line. This should be placed on the supply to the entire house in order to maintain equal hot and cold water pressures.

IMPORTANT: Heat cannot be applied to the water fittings on the heater as they may contain nonmetallic parts. If

Figure 13

Water Piping Installation

Hot Water

Outlet

Union

In a closed system use a thermal expansion tank

Cold Water Supply to Fixtures

 

 

 

 

 

 

 

Main

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water

 

 

 

 

 

 

 

Supply

 

 

 

 

 

 

 

Cold Water

 

Pressure reducing

 

Inlet Valve

 

valve with bypass

solder connections are used, solder the pipe to the adapter before attaching the adapter to the hot and cold water

Temperature and Pressure Relief Valve

fittings.

IMPORTANT: Always use a good grade of joint compound and be certain that all fittings are drawn up tight.

1.Install the water piping and fittings as shown in Figure 13. Connect the cold water supply (3/4” NPT) to the fitting marked “C”. Connect the hot water supply (3/4” NPT) to the fitting marked “H”.

IMPORTANT: Some models may contain energy saving heat traps to prevent the circulation of hot water within the pipes. Do not remove the inserts within the heat traps.

2.

The installation of unions in both the hot and cold water

 

supply lines is recommended for ease of removing the

 

water heater for service or replacement.

3.

The manufacturer of this water heater recommends

 

installing a tempering valve or an anti-scald device

 

in the domestic hot water line as shown in Figure 14.

 

These valves reduce the point-of-use temperature of

 

the water by mixing cold and hot water and are readily

 

available for use.

4.

If installing the water heater in a closed water system,

 

install an expansion tank in the cold water line as

 

specified under Closed System/Thermal Expansion.

5.

Install a shut-off valve in the cold water inlet line. It

 

should be located close to the water heater and be

1”minimum

Metal Drain Pan

1 3/4” depth maximum

Figure 14

Typical Tempering

Valve Installation

Follow the tempering valve manufacturer’s instructions.

Hot

Water

Outlet

Discharge line 6” maximum above drain

Drain line

 

3/4” ID

 

minimum

Massachusetts:

Drain

Install a vacuum relief

 

 

in cold water line per

 

 

section 19 MGL 142.

 

 

Cold

 

 

 

 

Water

 

 

Inlet

 

 

easily accessible. Know the location of this valve and

how to shut off the water to the heater.

6. A temperature and pressure relief valve must be

installed in the opening marked “Temperature and

Pressure (T & P) Relief Valve” on the water heater.

A discharge line must be added to the opening of

the T&P Relief Valve. Follow the instructions under

Temperature and Pressure Relief Valve.

Tempered water to fixtures

Tempering valve (Set to 120°F)

12

Page 12
Image 12
Whirlpool 315420-000, W10100910 warranty Water System Piping, Piping Installation