Special provisions for mobile home installations:
The exhaust vent must be securely fastened to a noncombustible portion of the mobile home structure and must not terminate beneath the mobile home. Terminate the exhaust vent outside.
Determine vent path:
■■Select route that will provide straightest and most direct path outdoors.
■■ Plan installation to use fewest number of elbows and turns.
■■ When using elbows or making turns, allow as much room as possible.
■■ Bend vent gradually to avoid kinking. ■■ Use as few 90° turns as possible.
Determine vent length and elbows needed for best drying performance:
■■Use following “Vent System Chart” to determine type of vent material and hood combinations acceptable to use.
NOTE: Do not use vent runs longer than those specified
in “Vent System Chart.” Exhaust systems longer than those specified will:
■■Shorten life of dryer.
■■Reduce performance, resulting in longer drying times and increased energy usage.
The “Vent System Chart” provides venting requirements that will help achieve best drying performance.
Vent System Chart
Number of | Type | Box/louvered | Angled |
90° turns | of vent | hoods | hoods |
or elbows |
|
|
|
0 | Rigid metal | 43 ft. (13.1 m) | 36 ft. (11.0 m) |
|
|
|
|
1 | Rigid metal | 33 ft. (10.1 m) | 26 ft. (7.9 m) |
|
|
|
|
2 | Rigid metal | 24 ft. (7.3 m) | 16 ft. (4.9 m) |
|
|
|
|
NOTE: Side exhaust installations have a 90º turn inside the dryer. To determine maximum exhaust length, add one 90º turn to the chart.
INSTALL VENT SYSTEM
1. Install exhaust hood
12" min.
(305 mm)
12" min. (305 mm)
Install exhaust hood and use caulking compound to seal exterior wall opening around exhaust hood.
2. Connect vent to exhaust hood
Vent must fit over the exhaust hood. Secure vent to exhaust hood with 4" (102 mm) clamp. Run vent to dryer location using straightest path possible. Avoid 90° turns. Use clamps to seal all joints. Do not use duct tape, screws, or other fastening devices that extend into interior of vent to secure vent, because they can catch lint.
17