7.

System low on

Check refrigerant “sight glass” in 1/4” tubing.

 

refrigerant.

Check for bubbles after system has run for several

 

 

 

minutes. If bubbles present, call a CERTIFIED HVAC

 

 

 

service technician. If sight is clear of bubbles,

 

 

 

refrigerant level is OK.

 

 

 

 

 

8.

Thermostatic

System will operate as if it were low on refrigerant

 

expansion valve power

charge. Sight glass will be clear. Evaporator coil icing

 

element losing its

probable.

 

charge.

Call a CERTIFIED HVAC service technician.

 

 

 

 

 

9.

Low voltage to

Low voltage will cause compressor overheating and

 

compressor, below

tripping on overload. Also, can have difficulty starting.

 

103V with compressor

This is usually a field wiring problem which should be

 

running.

corrected immediately.

 

 

 

 

 

10.

Cooling system not

If system is determined to run OK but not keeping up,

 

sufficient for load

run a heat gain calculation for the wine cellar and

 

 

 

compare with cooling system capacity.

 

 

 

Evaporator blower runs, but compressor does not

 

 

 

 

1.

System “Anti-Frost“

Observe for several minutes. Compressor should turn on

 

 

 

at termination of “Anti Frost“ Cycle and evaporator clear

 

 

 

of frost.

 

 

 

 

 

2.

Power off to

Check breaker/Refer to #3 above

 

compressor.

 

 

 

 

 

 

3.

Out of refrigerant.

Call a CERTIFIED HVAC service technician to locate leak,

 

 

 

repair and charge with refrigerant

 

 

 

 

 

4.

Compressor off on

Determine if compressor is hot. If not, there is another

 

overload.

problem. If yes, shut off power to condensing unit and

 

 

 

call service technician

 

 

 

 

 

5.

Liquid line solenoid

Remove cover. Locate valve in ¼” copper tube. Check

 

valve in evaporator not

to see if it is hot. If hot and you can feel a magnetic pull

 

active.

with a screwdriver, the valve is working. If cold, there is

 

 

 

no power to the valve coil. In this event, with the blower

 

 

 

running, the valve should be powered. Call a CERTIFIED

 

 

 

HVAC service technician.

 

 

 

 

 

6.

Thermostat

System will “pump down.” Compressor will stop.

 

expansion valve power

May start occasionally and shut off quickly.

 

element lost charge

Call a CERTIFIED HVAC service technician.

 

 

 

 