TROUBLESHOOTING

Fault Cause

Solution

Water leaking from unit

 

1. Condensate drain

Clear out drain

 

clogged

 

 

 

 

 

2. Evaporator coil

Clean the coil and / or fan wheel

 

frozen

 

 

 

 

 

3. Drain line improperly

Call a CERTIFIED HVAC service technician.

 

installed

 

 

 

 

Wine cellar temperature above thermostat set point

gj

1. Large quantity of

Allow time for wine to cool

warm wine placed in

 

cellar

 

2. Wine Cellar Door left

Close Door. Allow time for wine to cool.

open for long period.

 

3. No power to

Fan Coil

either fan coil unit or

Is the thermostat display illuminated?

condensing unit

If not, check power supply switch, if equipped. Ensure it

 

is in the ON position.

 

If on, check to see in the breaker is tripped.

 

If tripped, reset and check display.

 

If display “Wine” bar is illuminated, wait for time delay to

 

expire. Wine light blinks during time delay countdown.

 

Check to see if “On” bar indicator illumination appears

 

at which time the blower and cooling should start

 

If blower starts and no cooling follows, check power

 

supply to condensing unit.

 

Check breaker to condensing unit. If tripped, check to

 

see if compressor is hot – too hot to touch. If so, allow

 

to cool for one (1) hour before resetting breaker.

 

After cooling, reset breaker and note whether it remains

 

set or trips off. If it trips, call a CERTIFIED HVAC service

 

technician for repair.

 

 

-23-

Page 23
Image 23
WhisperKool SS7000, SS4000 owner manual Troubleshooting, Fault Cause Solution, Water leaking from unit, Fan Coil