SPECIFICATIONS
ELECTRICAL RATINGS [@ 77°F (25°C)]: Input Voltage: 25 VAC 50/60 Hz
Max. Input Current @ 25 VAC: 0.45 amp Relay Load Ratings:
Valve Relay: 1.5 amp @ 25 VAC 50/60 Hz 0.6 pf
Ignitor Relay: 6.0 amp @ 120 VAC 50/60 Hz (resistive)
Flame Current Requirements:
Minimum current to insure flame detection: 1 μa DC*
Maximum current for
Maximum allowable leakage resistance: 100 M ohms
*Measured with a DC microammeter in the flame probe lead
OPERATING TEMPERATURE RANGE:
HUMIDITY RANGE:
5% to 93% relative humidity
MOUNTING:
Surface mount multipoise |
|
Timing Specs: (@ 60 Hz**) |
|
| maximum |
Flame Establishing Time: | 0.8 sec |
Flame Failure Response Time: | 2.0 sec |
**At 50 Hz, all timing specifications should be increased by 20%
Gases Approved: Natural, Manufactured, Mixed, Liquid Petroleum, and LP Gas Air Mixtures are all approved for use.
TIMING SPECIFICATIONS
(All times are in seconds, unless noted otherwise)
| ||
|
| |
0 | ||
|
| |
INITIAL IGNITOR | 17 | |
|
| |
RETRY IGNITOR | 28 | |
|
| |
IGNITION ACTIVATION | 5 | |
PERIOD | ||
| ||
|
| |
TRIAL FOR IGNITION | 7 | |
PERIOD | ||
| ||
|
| |
RETRIES | 2 times | |
|
| |
VALVE SEQUENCE | 21 | |
PERIOD | ||
| ||
|
| |
INTERPURGE | 15 | |
|
| |
15 | ||
|
| |
LOCKOUT TIME | 200 | |
|
| |
DELAY TO HEAT ON | 30 | |
|
| |
DELAY TO HEAT OFF* | 60/90/ | |
120/180 | ||
| ||
|
| |
DELAY TO COOL ON | 0 | |
|
| |
DELAY TO COOL OFF | 45 | |
|
| |
AUTO RESET | 60 minutes | |
|
| |
HUMIDIFIER | YES | |
|
| |
ELECTRONIC AIR | YES | |
CLEANER | ||
| ||
|
|
*This time will vary depending on option switch position. The control is
2