SYSTEM LOCKOUT AND
DIAGNOSTIC FEATURES
SYSTEM LOCKOUT FEATURES
When system lockout occurs, the gas valve is
To reset the control after system lockout, do one of the following:
1.Interrupt the call for heat or cool at the thermostat for at least one second, but less than 20 seconds (if flame is sensed with the gas valve
2.Interrupt the 24 VAC power at the control for at least one second. You may also need to reset the flame rollout sensor switch.
3.After one hour in lockout, the control will automatically reset itself.
DIAGNOSTIC FEATURES
The 50A55 control continuously monitors its own opera- tion and the operation of the system. If a failure occurs, the LED will indicate a failure code as shown below. If the failure is internal to the control, the light will stay on continuously. In this case, the entire control should be replaced, as the control is not
If the sensed failure is in the system (external to the control), the LED will flash in the following
Continuous flashing | Low flame sense signal |
(no pause) |
|
1 flash, then pause | Lockout caused by flame sensed |
| when there should be no flame |
2 flashes, then pause | Pressure switch stuck closed |
3 flashes, then pause | Pressure switch stuck open |
4 flashes, then pause | High limit open |
5 flashes, then pause | Rollout switch open or rollout |
| sensed |
6 flashes, then pause | *Lockout caused by pressure |
| switch opening 4 times in one |
| cycle |
7 flashes, then pause | *Lockout caused by no ignition |
| (after 3 trials) |
8 flashes, then pause | *Lockout caused by loss of flame |
| 5 times in one heating cycle |
9 flashes, then pause | 115 Volt AC power reversed/ |
| improper ground |
12 flashes, then pause | Ignitor relay sense error |
The LED will also flash once at power-up.
*Will automatically restart from lockout after one hour. All other conditions need to be cleared for the control to resume normal operation.
7