Installing the Inverter/Charger

3.Press the INVERTER ENABLE button. Verify that the INVERTER ENABLED LED status light illuminates.

4.Connect the Freedom SW 230V to the test load by closing the AC breaker that controls the circuit that the test load is connected to.

If the light bulb illuminates, the Invert mode is working.

5.Press the Inverter Enable button to disable the inverter. The INVERTER ENABLED LED status light is off.

Testing in Charge Mode and AC Bypass Mode

1.Close the AC supply breaker to supply AC power to the unit.

To verify that the Freedom SW 230V starts charging:

2.After a few seconds, verify that the AC/Charge light on the front panel is turned on (indicating that the batteries are being charged).

To verify that Freedom SW 230V correctly switches to Bypass mode:

3.Disable the AC source and turn off the inverter by pressing the Inverter Enable button.

4.Connect the test load to the AC output connection of the unit.

5.Enable the AC source and the test load should turn on after ten seconds.

Installation Complete

Your installation is now complete. The Freedom SW 230V Inverter/ Charger is ready for use.

The preceding tests use a light test load (a light bulb) as a test case. If you encounter problems when using a load over 1000 watts (for example, a hair dryer or microwave), see the troubleshooting information in the Freedom SW 230V Sine Wave Inverter/Charger Owner’s Guide.

40

Freedom SW 230V Installation Guide

Page 54
Image 54
Xantrex Technology 815-3524, 815-2524-02 manual Testing in Charge Mode and AC Bypass Mode, Installation Complete