GFCI Requirements

A GFCI (ground fault circuit interrupter) is a device that de- energizes a circuit when a current to ground exceeds a specified value that is less than that required to open the circuit breaker. GFCIs are intended to protect people from electric shocks and are usually required in wet or damp locations.

Installation in recreational vehicles may require GFCI protection of certain branch circuits. Consult all applicable codes.

Disconnect Devices

Each system requires a method of disconnecting the AC circuits. If the overcurrent protection device is a circuit breaker, it will also serve as the disconnect. If fuses are used, separate AC disconnect switches will be needed between the source and the fuses.

975-0697-01-01

Planning Preparations

Distribution Panels

Some systems incorporate distribution panels both ahead of the

 

inverter/charger (the AC source panel) and between the inverter/

 

charger and the loads (the AC load panel). The AC source panel

 

includes a main circuit breaker, which serves as overcurrent

 

protection for the panel. Additional circuit breakers serve individual

only.

circuits, one of which serves the inverter/charger.

AC Wiring

personnel

 

Definition AC wiring includes input wiring (all the wires and

qualified

AC load panels, circuit breakers, and loads).

connectors between the AC source and the inverter/charger input)

 

and output wiring (all the wires between the inverter/charger and the

 

Type The type of wiring required varies according to the electrical

by

use

codes or regulations applicable to your installation. For RV

applications, this may be solid wire in multi-conductor cables, but

for

stranded wire is required if single conductors are used. All wiring

guide

must be rated 75 °C or higher. In Australia, all wiring must be rated

 

90 °C or higher.

This

Size of AC Input Wiring Wire size must be coordinated with the

 

overcurrent protection provided ahead of the wire involved, in accordance with the electrical codes or regulations applicable to your installation. Therefore, the wiring used between the AC input circuit breaker and the inverter/charger input must be sized to match the input breaker rating.