Installation
DC Wiring
The success of
Battery Requirements for
When inverters are “stacked” they must operate from a common battery bank. In other words, the DC negative of one inverter must be common with the second inverter and likewise for the DC positive.
For example:
If you have eight
When using inverters in a stacked configuration, the same battery bank must be used for both inverters. To ensure even charging of the batteries, each inverter must be connected to both strings (i.e., positive cable to string two, and negative cable to string one for inverter 1, and positive cable to string one and negative cable to string two for inverter 2) as shown in Figure
Refer to the Owner’s Manual for the Sine Wave Plus to determine the correct size and length of cable required.
DC conduit for | DC conduit for |
L2 Inverter | L1 Inverter |
– | + | – | + | Series String 1 |
| 12 Volt | 12 Volt |
| 24 Vdc/200 Ah |
| Battery |
|
| |
Battery |
|
| ||
200 Ah |
|
| ||
wired in Parallel | 200 Ah |
|
| |
|
|
| ||
24 Vdc/400 Ah |
|
|
|
|
|
|
|
| Series String 2 |
– | + | – | + | 24 Vdc/200 Ah |
| 12 Volt | 12 Volt |
|
|
| Battery | Battery |
|
|
| 200 Ah | 200 Ah |
|
|
Figure