Installation
Wiring for a 240
A 240 Vac source does not allow for the connection to the input of a 120 Vac inverter as no neutral line is supplied from the utility or generator. In order to use stacked inverters, a neutral line must be added by using a
The
To wire the inverters for a
1.Run GROUND wires (green):
a)from the AC Distribution Panel to the primary earth/ground connection.
b)from the generator ground to the AC Distribution Panel ground.
c)from the ground terminal in the Autotransformer to the AC Distribution Panel.
d)from the AC Distribution Panel to the Ground bar in the L1 inverter.
e)from the AC Distribution Panel to the Ground bar in the L2 inverter.
2.Run NEUTRAL wires (white):
a)from the
b)from the
c)from the NEUTRAL OUT on the L1 inverter to the NEUTRAL 2 terminal on the L2 inverter.
d)from the Neutral OUT on the L2 inverter to the Neutral terminal in the AC Distribution Panel.
3.Run HOT wires:
a)(black) from the L1 Output in the generator to the L1 terminal in the Autotransformer.
b)(black) from the L1 output terminal in the Autotransformer to the AC2 GEN terminal in the L1 inverter.
c)(black) from the INV OUT terminal in the L1 inverter to the L1 input terminal in the AC Distribution Panel.
d)(red) from the L2 Output in the generator to the L2 terminal in the Autotransformer.
e)(red) from the L2 output terminal in the Autotransformer to the AC2 GEN terminal in the L2 inverter.
f)(red) from the INV OUT terminal in the L2 inverter to the L2 input terminal in the AC Distribution Panel.
4.Torque all inverter terminal block connections to 25