 | Troubleshooting Reference | |||||||
| 
 | Table  | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | Problem | Possible Cause | Solution | |||||||||||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | No output voltage. No | The switch is in Standby ( ) | Turn the On/Standby switch to On ( | 
 | ). | 
 | ||||||||
| 
 | 
 | 
 | ||||||||||||
| 
 | indicator lights are | mode. | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | illuminated. | 
 | Check the DC wiring to the inverter for | |||||||||||
| 
 | 
 | No input power to the inverter. | ||||||||||||
| 
 | 
 | 
 | loose connections, frayed wiring or an | |||||||||||
| 
 | 
 | 
 | open DC Disconnect. | |||||||||||
| 
 | 
 | DC fuse open (external) | Have a qualified service technician | |||||||||||
| 
 | 
 | 
 | check and replace the fuse. | |||||||||||
| 
 | No output voltage. Inverter | Supplemental Circuit | Disconnect all appliances to reduce the | 
 | ||||||||||
| 
 | ON light is illuminated. | Protection button has tripped. | overload. Check the AC wiring, and | |||||||||||
| 
 | 
 | 
 | reset the Supplemental Circuit | |||||||||||
| 
 | 
 | 
 | Protection button. | |||||||||||
| 
 | 
 | GFCI has tripped. | Clear the ground fault, and reset the | |||||||||||
| 
 | 
 | 
 | GFCI by pressing the Reset button on | |||||||||||
| 
 | 
 | 
 | the GFCI. | |||||||||||
| 
 | No output voltage. Fault light | Inverter may be overloaded. | Disconnect all appliances connected to | 
 | ||||||||||
| 
 | is illuminated. | 
 | the inverter, and reset the inverter by | |||||||||||
| 
 | 
 | 
 | turning the On/Standby switch to | |||||||||||
| 
 | 
 | Battery voltage may be too | Standby ( | 
 | 
 | 
 | ) and then to On ( | 
 | ). | |||||
| 
 | 
 | 
 | 
 | 
 | 
 | |||||||||
| 
 | 
 | The inverter will restart if the battery | ||||||||||||
| 
 | 
 | high. | voltage drops below 14.5 volts DC. | |||||||||||
| 
 | 
 | Over temperature. | Allow the inverter to cool down. The | |||||||||||
| 
 | 
 | 
 | inverter will restart automatically. | |||||||||||
| 
 | No output voltage. Low | Battery voltage is too low. | Recharge the battery to more than 12.6 | 
 | ||||||||||
| 
 | Battery light is illuminated. | 
 | volts DC. The inverter will restart | |||||||||||
| 
 | 
 | 
 | automatically. | |||||||||||
| 
 | 
 | Poor DC wiring. | Turn the inverter to Standby ( | 
 | ). | |||||||||
| 
 | 
 | 
 | ||||||||||||
| 
 | 
 | 
 | ||||||||||||
| 
 | 
 | 
 | Disconnect the DC wiring. Use proper | |||||||||||
| 
 | 
 | 
 | wiring and ensure all connections are | |||||||||||
| 
 | 
 | 
 | tight. | |||||||||||
| 
 | Output voltage is present. | Battery voltage is low. | Disconnect all appliances. Charge the | 
 | ||||||||||
| 
 | Inverter ON light and Low | 
 | batteries. | |||||||||||
| 
 | Battery light are illuminated. | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 