Table 3-1Troubleshooting Reference (Continued)

Problem

Possible Cause

Solution

 

 

 

 

 

 

 

AC input cord is connected to

The shore power voltage is out

Turn the On/Standby switch to On (

 

),

 

shore power, but the

of range (less than 85 volts AC

and the appliance will be powered from

appliance is not powered

or greater than 140 volts AC).

the inverter.

from shore power. AC Input

 

 

 

 

 

 

light is off.

External breaker has tripped.

Reset the external breaker.

 

AC input cord is connected to

Supplemental circuit breaker

Disconnect all appliances. Check the

shore power, but the

has tripped.

AC wiring and press the Supplemental

appliance is not powered

 

Circuit Protection button to reset it.

from shore power. AC Input

 

Correct the ground fault and reset the

light is illuminated.

GFCI has tripped.

 

 

GFCI.

AC input cord is connected to

The shore power voltage is

Turn On/Standby switch to On (

 

), and

 

shore power. AC Input light

close to being out of range (less

the appliance will be powered from the

illuminates intermittently.

than 85 volts AC or greater

inverter or shore power.

 

than 140 volts AC).

 

 

 

 

 

Fan does not turn on.

The internal components of the

No action. The fan will run

 

inverter are not warm.

automatically when necessary to cool

 

 

the internal components of the inverter.

Fan runs all the time.

The amount of power being

No action. The fan will run at lower

 

consumed by the appliances is

speeds and stop automatically when the

 

high.

internal temperature of the inverter

 

 

falls.

 

The ambient temperature is

No action. The fan will run at lower

 

high.

speeds and stop automatically when the

 

 

ambient temperature falls.

 

 

For more information on the “Fan

 

 

Cooling System”, refer to page A–3

 

 

 

 

 

 

 

3–4

445-0167-01-01