SITE REQUIREMENTS
1. FLUE OUTLET POSITIONS
Terminal
Flue
Vertical
Measurement
Horizontal
Measurement
150mm
max
Adjacent
Building
Insulation
|
|
| The vertical measurement is the lowest from either the | |
|
|
| point of discharge or 150mm above insulation. | |
|
|
|
| IMPORTANT: Seek specialist |
| Position On Roof | Minimum Clearances |
| |
|
| advice if installing in a dwelling | ||
|
|
|
| |
|
|
|
| |
A | On ridge or within 600mm | 600mm above ridge |
| with a thatched roof |
B | Elsewhere on roof | 2300mm horizontally from roof surface and: |
| |
|
| a) 1000mm above highest point of flue exit |
|
|
|
| from roof or |
|
|
|
| b) as high as the ridge |
|
|
|
|
|
|
|
C | On pitched, within 2300mm horizontally to | 1000mm above top of opening |
|
|
| openable window, dormer |
|
|
|
D | Within 2300mm of another building | 600mm above top of building |
|
|
1. HEARTH DIMENSIONS
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 150mm |
|
|
|
|
|
|
| 150mm | ||
|
|
|
|
|
|
| 150mm | |||||
|
| minimum |
|
| 225mm |
| minimum | |||||
|
|
|
|
| minimum | |||||||
|
|
|
|
|
| minimum |
|
|
| |||
|
|
|
|
|
|
| Constructional Hearth | |||||
| Constructional Hearth | 840mm minimum | ||||||||||
|
| 840mm minimum |
|
|
| PR7205 | ||||||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
2.1The appliance must stand on a constructional hearth which is at least 125mm thick with the minimum dimensions as shown in the diagram opposite.
2.2The building must have a suitable
Caution: These appliances are heavy.
2.3When fitting into an existing hearth check that the appliance complies with current construction regulations and is at least the minimum sizes shown.
2.4If there is no existing fireplace or chimney it is possible to construct a suitable
18