035-16703-001-A-0202

TABLE 5 - ELECTRICAL DATA (COOLING / ELECTRIC HEAT)

DEB

 

COMPRESSOR

COND.

SUPPLY

ELECTRIC HEAT ACCESSORY

 

MAX.

MAX.

 

 

 

 

 

 

 

 

MINIMUM

 

POWER

 

 

FAN

AIR

 

 

 

 

 

FUSE

HACR2

MODEL

SUPPLY

 

 

MOTOR

BLOWER

 

STAGE

 

 

 

CIRCUIT

SIZE,1

BREAKER

 

 

 

FLA

MOTOR,

 

 

 

TOTAL

AMPACITY

AMPS

SIZE

 

 

RLA

LRA

FLA

MODEL NO.

 

KW

 

 

 

 

 

 

 

AMPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

018

208/230-1-60

9.0

48.0

1.1

2.6

2NH04500506

1

3.8/5.0

*

18.1/20.8

25.8/29.3

30/30

30/30

2NH04500706

2

5.6/7.5

*

27.1/31.3

37.1/42.3

40/45

40/45

 

 

 

 

 

 

 

 

 

 

 

 

2NH04500506

1

3.8/5.0

*

18.1/20.8

25.8/29.3

30/30

30/30

024

208/230-1-60

11.2

60.0

1.1

2.6

2NH04500706

2

5.6/7.5

*

27.1/31.3

37.1/42.3

40/45

40/45

 

 

 

 

 

 

2NH04501006

2

7.5/10.0

*

36.1/41.7

48.4/55.3

50/60

50/60

 

 

 

 

 

 

2NH04500506

1

3.8/5.0

*

18.1/20.8

25.8/29.3

30/30

30/30

030

208/230-1-60

12.0

73.0

1.1

2.6

2NH04500706

2

5.6/7.5

*

27.3/31.3

37.1/42.3

40/45

40/45

2NH04501006

2

7.5/10.0

*

36.1/41.7

48.4/55.3

50/60

50/60

 

 

 

 

 

 

 

 

 

 

 

 

2NH04501506

2

11.3/15.0

*

54.2/62.5

71.0/81.4

80/90

80/90

036

208/230-1-60

17.3

94.0

1.1

3.5

2NH04501006

2

7.5/10.0

*

36.1/41.7

49.5/56.5

50/60

50/60

2NH04501506

2

11.3/15.0

*

54.2/62.5

72.1/82.5

80/90

80/90

 

 

 

 

 

 

 

 

 

 

 

 

2NH04500506

1

3.8/5.0

*

18.1/20.8

30.2/30.4

40/40

40/40

042

208/230-1-60

20.5

120.0

1.1

3.5

2NH04500706

2

5.6/7.5

*

27.1/31.3

38.2/43.4

50/50

50/50

2NH04501006

2

7.5/10.0

*

36.1/41.7

49.5/56.5

50/60

50/60

 

 

 

 

 

 

 

 

 

 

 

 

2NH04501506

2

11.3/15.0

*

54.2/62.5

72.1/82.5

80/90

80/90

 

 

 

 

 

 

2NH04501006

2

7.5/10.0

*

36.1/41.7

50.1/57.1

60/60

60/60

048

208/230-1-60

24.4

140.0

1.3

4.0

2NH04501506

2

11.3/15.0

*

54.2/62.5

72.1/83.1

80/90

80/90

2NH04502006

2

15.0/20.0

*

72.2/83.3

95.3/109.2

100/110

100/110

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502506

2

18.8/25.0

*

90.3/104.2

117.8/135.2

125/150

125/150

 

 

 

 

 

 

2NH04501006

2

7.5/10.0

*

36.1/41.7

53.9/60.8

70/70

70/70

060

208/230-1-60

28.9

165.0

1.3

7.0

2NH04501506

2

11.3/15.0

*

54.2/62.5

76.5/86.9

80/90

80/90

2NH04502006

2

15.0/20.0

*

72.2/83.3

99.0/112.9

100/125

100/125

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502506

2

18.8/25.0

*

90.3/104.2

121.6/139.0

125/150

125/150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

208/230-3-60

10.9

78.0

1.1

3.5

2NH04501025

1

7.5/10.0

*

20.8/24.1

30.4/34.4

35/35

35/35

2NH04501525

1

11.3/15.0

*

31.3/36.1

43.5/49.5

45/50

45/50

 

 

 

 

 

 

042

208/230-3-60

14.1

110.0

1.1

3.5

2NH04501025

1

7.5/10.0

*

20.8/24.1

30.4/34.4

35/35

35/35

2NH04501525

1

11.3/15.0

*

31.3/36.1

43.5/49.5

45/50

45/50

 

 

 

 

 

 

 

 

 

 

 

 

2NH04501025

1

7.5/10.0

*

20.8/24.1

31.1/35.1

35/40

35/40

048

208/230-3-60

14.1

105.0

0.7

4.0

2NH04501525

1

11.3/15.0

*

31.3/36.1

44.1/50.1

45/60

45/60

2NH04502025

2

15.0/20.0

*

41.7/48.1

57.1/65.1

60/70

60/70

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502525

2

18.8/25.0

*

52.1/60.1

70.2/80.2

80/90

80/90

 

 

 

 

 

 

2NH04501025

1

7.5/10.0

*

20.8/24.1

34.8/38.8

40/40

40/40

060

208/230-3-60

16.0

125.0

1.3

7.0

2NH04501525

1

11.3/15.0

*

31.3/36.1

47.8/53.9

50/60

50/60

2NH04502025

2

15.0/20.0

*

41.7/48.1

60.9/68.9

70/70

70/70

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502525

2

18.8/25.0

*

52.1/60.1

73.9/83.9

80/90

80/90

036

460-3-60

5.8

40.0

0.6

1.8

2NH04501046

1

10.0 **

12.0

17.3

20

20

2NH04501546

1

15.0 **

18.0

24.8

25

25

 

 

 

 

 

 

042

460-3-60

7.1

54.0

0.6

1.8

2NH04501046

1

10.0 **

12.0

17.3

20

20

2NH04501546

1

15.0 **

18.0

24.8

25

25

 

 

 

 

 

 

 

 

 

 

 

 

2NH04501046

1

10.0 **

12.0

17.5

20

20

048

460-3-60

7.1

55.0

0.6

2.0

2NH04501546

1

15.0 **

18.0

25.1

30

30

2NH04502046

2

20.0 **

24.1

32.6

35

35

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502546

2

25.0 **

30.1

40.1

45

45

 

 

 

 

 

 

2NH04501046

1

10.0 **

12.0

19.4

20

20

060

460-3-60

8.0

67.0

0.7

3.5

2NH04501546

1

15.0 **

18.0

26.9

30

30

2NH04502046

2

20.0 **

24.1

34.4

35

35

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502546

2

25.0 **

30.1

42.0

45

45

 

 

 

 

 

 

 

 

 

 

 

 

 

036

575-3-60

4.5

32.0

0.4

1.5

2NH04501058

1

10.0 ***

9.6

13.9

15

15

2NH04501558

1

15.0 ***

14.4

19.9

20

20

 

 

 

 

 

 

042

575-3-60

5.8

44.0

0.4

1.5

2NH04501058

1

10.0 ***

9.6

13.9

15

15

2NH04501558

1

15.0 ***

14.4

19.9

20

20

 

 

 

 

 

 

 

 

 

 

 

 

2NH04501058

1

10.0 ***

9.6

14.0

15

15

048

575-3-60

5.6

44.0

0.6

1.6

2NH04501558

1

15.0 ***

14.4

20.0

25

25

2NH04502058

2

20.0 ***

19.2

26.1

30

30

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502558

2

25.0 ***

24.1

32.1

35

35

 

 

 

 

 

 

2NH04501058

1

10.0 ***

9.6

15.5

20

20

060

575-3-60

6.4

50.0

0.6

2.8

2NH04501558

1

15.0 ***

14.4

21.5

25

25

2NH04502058

2

20.0 ***

19.2

27.6

30

30

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502558

2

25.0 ***

24.1

33.6

35

35

1= Dual element, time delay type.

2= Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.

*= KW listed is for 240 volts, use table on previous page for 208 or 230 volts. ** = KW listed is for 480 volts, use table on previous page for 460 volts.

*** = KW listed is for 600 volts, use table on previous page for 575 volts.

6

Unitary Products Group

Page 6
Image 6
York D1EB018 THRU 060, 1-1/2 THRU 5 TON (10 SEER) installation instructions Electrical Data Cooling / Electric Heat