4918

035-16703-001-A-0202

HIGH78VOLTAGE CONN. 2814" DIA. KNOCKOUT

HIGH13132VOLTAGE CONN.

4714 " DIA. KNOCKOUT

LOW78VOLTAGE CONN.

 

 

 

 

 

“ DIA. KNOCKOUT

4918

 

 

 

 

SIDE SUPPLY

 

 

3

34

AIR OPENING

 

 

 

2814

 

SIDE RETURN

 

 

AIR OPENING

 

22141714

 

(OVERALL)

 

 

LOW78VOLTAGE CONN.

 

 

 

 

 

“ DIA. KNOCKOUT

 

 

 

 

 

FRONT

COMPRESSOR

 

 

 

SERVICE ACCESS

 

 

 

COMPARTMENT PANEL

3

“A”

UNIT SIZE

DIMENSION

 

(OVERALL)

“A”

 

33 12

2 8

4714

018 - 042

 

 

048 - 060

4112

2814

 

REFRIGERANT

 

 

CONNECTIONS

 

 

ELECTRICAL/FILTER

 

 

SERVICE ACCESS

 

 

COMPARTMENT PANEL

17142214

 

HIGH12364VOLTAGE CONN.

2 121

 

" DIA. KNOCKOUT

(OVERALL)

 

 

 

 

 

FRONT

4312

4012

2634

6

2212

 

 

 

 

 

OUTDOOR

 

 

 

CONDENSATE

COIL

 

 

 

 

 

 

 

 

DRAIN 34“ NPTI

 

 

 

 

 

 

BOTTOM SUPPLY

 

 

 

 

AIR OPENING

 

 

 

 

13

4

11217142214

426342

HIGH VOLTAGE

CONN. 131322212 “ x78“ DIA.

KNOCKOUT

UNIT CONDENSATE

 

 

CONNECTION 34“ NPTI

 

 

(TRAP REQUIRED)

AIR12841OPENING328

 

 

 

1412

 

 

All dimensions are in inches. They are

subject to change without notice. Certified

dimensions will be provided upon request.

 

 

 

SIDE SUPPLY

38BACK

 

3

 

3

 

 

 

 

SIDE RETURN

2

8

 

1412

AIR OPENING

 

 

 

 

CLEARANCES

(Minimum)

Front

12"

Back

0"

Left Side (Filter Access)

24"

Right Side

24"

Below Unit1

0"

Above Unit2

36" (For Condenser

 

Air Discharge)

 

 

 

3

15

312

15

28916

312

 

 

4

 

15

3

1 4

 

 

 

 

 

 

 

BOTTOM RETURN

 

 

 

 

 

AIR OPENING

114124

1Units may be installed on combustible floors made from wood or class A, B or C roof covering material.

2Units must be installed outdoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet.

FIG. 3 - DIMENSIONS AND CLEARANCES

10

Unitary Products Group

Page 10
Image 10
York D1EB018 THRU 060, 1-1/2 THRU 5 TON (10 SEER) 1412, 2814, 17142214, 4714, 2212, Dimensions And Clearances, 4918, 2634

FAQ

What are the minimum clearances for installation?

The minimum clearances for installation are 12" in the front, 0" in the back, 24" on the left side for filter access, and 24" on the right side.

Can the units be installed on combustible floors?

Yes, units may be installed on combustible floors made from wood or class A,B or C roof covering material.

Where can the units be installed?

Units must be installed outdoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet.