035-16703-001-A-0202

TABLE 6 - SUPERHEAT CHARGING TABLE FOR MODEL D1EB018

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 600 CFM/TON

 

 

TEMPERATURE

 

 

 

 

INDOOR WB TEMPERATURE (F)

 

 

 

 

(F)

55

57

59

61

63

65

67

69

71

73

75

 

65

17.8

19.8

21.8

23.9

25.9

27.9

29.9

31.1

32.3

33.6

34.8

70

12.2

14.9

17.5

20.2

22.8

25.4

28.1

29.3

30.6

31.9

33.1

75

6.6

9.9

13.2

16.4

19.7

23.0

26.3

27.6

28.9

30.2

31.5

85

-

-

-

9.0

13.6

18.1

22.6

24.0

25.4

26.8

28.3

90

-

-

-

8.0

12.0

16.0

19.9

21.7

23.4

25.1

26.8

95

-

-

-

6.9

10.4

13.8

17.3

19.3

21.3

23.3

25.3

100

-

-

-

5.3

8.0

10.6

13.3

16.0

18.7

21.4

24.1

105

-

-

-

-

5.5

7.4

9.2

12.7

16.1

19.5

22.9

110

-

-

-

-

-

-

5.2

9.3

13.4

17.6

21.7

115

-

-

-

-

-

-

-

6.0

10.8

15.7

20.5

TABLE 7 - SUPERHEAT CHARGING TABLE FOR MODEL D1EB024

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 800 CFM/TON

 

 

TEMPERATURE

 

 

 

 

INDOOR WB TEMPERATURE (F)

 

 

 

 

(F)

55

57

59

61

63

65

67

69

71

73

75

 

65

13.5

15.0

16.5

18.0

19.6

21.1

22.6

23.9

25.3

26.6

27.9

70

10.1

11.8

13.5

15.2

16.9

18.6

20.3

21.9

23.4

25.0

26.5

75

6.7

8.6

10.5

12.4

14.3

16.2

18.1

19.8

21.6

23.4

25.2

80

-

5.4

7.5

9.6

11.6

13.7

15.8

17.8

19.8

21.8

23.8

85

-

-

-

6.7

9.0

11.2

13.5

15.7

17.9

20.2

22.4

90

-

-

-

6.3

8.3

10.3

12.3

14.5

16.7

19.0

21.2

95

-

-

-

6.0

7.6

9.3

11.0

13.3

15.5

17.8

20.0

100

-

-

-

5.3

6.6

7.8

9.1

11.1

13.1

15.0

17.0

105

-

-

-

-

5.5

6.4

7.2

8.9

10.6

12.3

14.0

110

-

-

-

-

-

-

5.3

6.7

8.2

9.6

11.0

115

-

-

-

-

-

-

-

-

5.7

6.8

8.0

TABLE 8 - SUPERHEAT CHARGING TABLE FOR MODEL D1EB030

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 1,000 CFM/TON

 

 

TEMPERATURE

 

 

 

 

 

INDOOR WB TEMPERATURE (F)

 

 

 

 

 

(F)

55

57

 

59

61

63

65

67

69

71

 

73

75

 

 

 

65

21.6

22.5

 

23.4

24.3

25.3

26.2

27.1

27.5

28.0

 

28.4

28.8

70

18.0

19.3

 

20.5

21.7

23.0

24.2

25.4

26.0

26.6

 

27.1

27.7

75

14.5

16.0

 

17.6

19.1

20.7

22.2

23.8

24.5

25.2

 

25.9

26.6

80

11.0

12.8

 

14.7

16.5

18.4

20.3

22.1

23.0

23.8

 

24.7

25.5

85

7.4

9.6

 

11.8

14.0

16.1

18.3

20.5

21.5

22.4

 

23.4

24.4

90

-

5.6

 

7.9

10.3

12.6

15.0

17.3

18.8

20.3

 

21.9

23.4

95

-

-

 

-

6.6

9.1

11.6

14.1

16.2

18.3

 

20.3

22.4

100

-

-

 

-

5.4

7.2

9.1

10.9

13.5

16.1

 

18.7

21.3

105

-

-

 

-

-

5.3

6.6

7.8

10.9

14.0

 

17.1

20.3

110

-

-

 

-

-

-

-

-

8.3

11.9

 

15.5

19.2

115

-

-

 

-

-

-

-

-

5.7

9.8

 

14.0

18.1

TABLE 9 - SUPERHEAT CHARGING TABLE FOR MODEL D1EB036

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 1,200 CFM/TON

 

 

TEMPERATURE

 

 

 

 

 

INDOOR WB TEMPERATURE (F)

 

 

 

 

 

(F)

55

57

 

59

61

63

65

67

69

71

 

73

75

 

 

 

65

11.5

13.4

 

15.4

17.4

19.4

21.4

23.4

24.6

25.9

 

27.1

28.4

70

9.3

11.4

 

13.4

15.5

17.6

19.6

21.7

23.3

24.9

 

26.4

28.0

75

7.1

9.3

 

11.4

13.6

15.8

17.9

20.1

22.0

23.9

 

25.7

27.6

80

-

7.2

 

9.4

11.7

13.9

16.2

18.4

20.6

22.8

 

25.1

27.3

85

-

5.1

 

7.5

9.8

12.1

14.5

16.8

19.3

21.8

 

24.4

26.9

90

-

5.5

 

7.4

9.2

11.0

12.8

14.6

17.6

20.6

 

23.6

26.5

95

-

5.9

 

7.3

8.6

9.9

11.2

12.5

15.9

19.3

 

22.8

26.2

100

-

5.5

 

6.6

7.8

9.0

10.2

11.4

15.0

18.5

 

22.1

25.6

105

-

-

 

6.0

7.1

8.2

9.3

10.3

14.0

17.7

 

21.4

25.1

110

-

-

 

5.4

6.4

7.3

8.3

9.2

13.1

16.9

 

20.7

24.5

115

-

-

 

-

5.7

6.5

7.3

8.1

12.1

16.1

 

20.0

24.0

8

Unitary Products Group

Page 8
Image 8
York D1EB018 THRU 060, 1-1/2 THRU 5 TON (10 SEER) installation instructions 035-16703-001-A-0202

FAQ

What is the airflow for the superheat charging tables?

The airflow for the superheat charging tables is 600 CFM/TON for model D1EB018, 800 CFM/TON for model D1EB024, 1,000 CFM/TON for model D1EB030, and 1,200 CFM/TON for model D1EB036.

What temperature range is covered in the superheat charging tables?

The temperature range covered in the superheat charging tables is from 55°F to 115°F for various indoor wet bulb temperatures.

What is the purpose of the superheat charging tables?

The superheat charging tables provide guidelines for adjusting refrigerant levels in York air conditioners to optimize performance under different operating conditions.