TABLE 10 - SUPERHEAT CHARGING TABLE FOR MODEL D1EB042

 

 

 

 

 

 

 

 

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 1,400 CFM/TON

 

 

 

 

TEMPERATURE

 

 

 

 

 

INDOOR WB TEMPERATURE (F)

 

 

 

 

 

 

 

(F)

55

57

 

59

61

63

65

67

69

71

 

73

 

75

 

 

 

 

 

 

65

20.3

21.9

 

23.5

25.0

26.6

28.1

29.7

30.6

31.6

 

32.6

 

33.6

 

70

16.7

18.5

 

20.3

22.1

23.9

25.7

27.5

28.6

29.7

 

30.8

 

32.0

 

75

13.0

15.1

 

17.1

19.2

21.2

23.2

25.3

26.6

27.8

 

29.1

 

30.4

 

80

9.4

11.7

 

13.9

16.2

18.5

20.8

23.1

24.5

25.9

 

27.3

 

28.7

 

85

5.7

8.2

 

10.8

13.3

15.8

18.4

20.9

22.5

24.0

 

25.6

 

27.1

 

90

-

6.5

 

9.1

11.7

14.2

16.8

19.4

21.0

22.6

 

24.1

 

25.7

 

95

-

-

 

7.4

10.0

12.7

15.3

17.9

19.5

21.1

 

22.7

 

24.3

 

100

-

-

 

5.8

7.9

10.0

12.0

14.1

16.3

18.4

 

20.6

 

22.8

 

105

-

-

 

-

5.8

7.3

8.7

10.2

13.0

15.8

 

18.6

 

21.4

 

110

-

-

 

-

-

-

5.5

6.4

9.8

13.2

 

16.5

 

19.9

 

115

-

-

 

-

-

-

-

-

6.5

10.5

 

14.5

 

18.5

 

TABLE 11 - SUPERHEAT CHARGING TABLE FOR MODEL D1EB048

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 1,600 CFM/TON

 

 

 

 

TEMPERATURE

 

 

 

 

 

INDOOR WB TEMPERATURE (F)

 

 

 

 

 

 

 

(F)

55

57

 

59

61

63

65

67

69

71

 

73

 

75

 

 

 

 

 

 

65

13.5

15.4

 

17.3

19.1

21.0

22.8

24.7

26.1

27.6

 

29.0

 

30.5

 

70

10.7

12.7

 

14.7

16.8

18.8

20.9

22.9

24.7

26.5

 

28.2

 

30.0

 

75

7.8

10.0

 

12.2

14.5

16.7

18.9

21.2

23.3

25.4

 

27.5

 

29.6

 

80

-

7.3

 

9.7

12.1

14.5

17.0

19.4

21.8

24.2

 

26.7

 

29.1

 

85

-

-

 

7.2

9.8

12.4

15.0

17.6

20.4

23.1

 

25.9

 

28.6

 

90

-

-

 

6.1

7.7

9.4

11.0

12.7

16.6

20.5

 

24.4

 

28.3

 

95

-

-

 

-

5.7

6.3

7.0

7.7

12.7

17.8

 

22.8

 

27.9

 

100

-

-

 

-

5.3

5.9

6.5

7.1

11.1

15.1

 

19.1

 

23.0

 

105

-

-

 

-

-

5.5

6.0

6.6

9.5

12.4

 

15.3

 

18.2

 

110

-

-

 

-

-

5.0

5.5

6.0

7.8

9.7

 

11.6

 

13.4

 

115

-

-

 

-

-

-

-

5.4

6.2

7.0

 

7.8

 

8.6

 

TABLE 12 - SUPERHEAT CHARGING TABLE FOR MODEL D1EB060

 

 

 

 

 

 

 

 

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 2,000 CFM/TON

 

 

 

 

TEMPERATURE

 

 

 

 

 

INDOOR WB TEMPERATURE (F)

 

 

 

 

 

 

 

(F)

55

57

 

59

61

63

65

67

69

71

 

73

 

75

 

 

 

 

 

 

65

25.3

25.8

 

26.3

26.8

27.3

27.8

28.3

28.7

29.1

 

29.6

 

30.0

 

70

22.2

23.0

 

23.7

24.4

25.1

25.9

26.6

27.4

28.2

 

28.9

 

29.7

 

75

19.2

20.1

 

21.1

22.1

23.0

24.0

24.9

26.1

27.2

 

28.3

 

29.4

 

80

16.1

17.3

 

18.5

19.7

20.9

22.1

23.3

24.7

26.2

 

27.7

 

29.1

 

85

13.1

14.5

 

15.9

17.3

18.8

20.2

21.6

23.4

25.2

 

27.0

 

28.9

 

90

10.3

11.7

 

13.1

14.5

15.9

17.3

18.6

21.1

23.5

 

25.9

 

28.3

 

95

7.6

8.9

 

10.3

11.6

13.0

14.3

15.7

18.7

21.8

 

24.8

 

27.8

 

100

6.6

7.7

 

8.9

10.1

11.3

12.5

13.6

16.7

19.7

 

22.7

 

25.8

 

105

5.6

6.6

 

7.6

8.6

9.6

10.6

11.6

14.6

17.6

 

20.7

 

23.7

 

110

-

5.4

 

6.2

7.0

7.9

8.7

9.5

12.5

15.6

 

18.6

 

21.6

 

115

-

-

 

-

5.5

6.2

6.8

7.5

10.5

13.5

 

16.5

 

19.5

 

Unitary Products Group

9

Page 9
Image 9
York 1-1/2 THRU 5 TON (10 SEER), D1EB018 THRU 060 installation instructions Outdoor

FAQ

What is the outdoor temperature superheat at 65°F indoor temperature?

For York D1EB042 model, the superheat at 65°F indoor temperature is 20.3°F.

What is the outdoor temperature superheat at 80°F indoor temperature for York D1EB048 model?

The superheat at 80°F indoor temperature for York D1EB048 model is 16.1°F.

What is the superheat at 95°F outdoor temperature and 55°F indoor temperature for York D1EB060 model?

The superheat at 95°F outdoor temperature and 55°F indoor temperature for York D1EB060 model is 7.6°F.