York D1EB018 THRU 060 Power And Control Wiring, Compressors, Typical Field Wiring Diagram

Models: 1-1/2 THRU 5 TON (10 SEER) D1EB018 THRU 060

1 17
Download 17 pages 47.79 Kb
Page 4
Image 4
POWER AND CONTROL WIRING

035-16703-001-A-0202

POWER AND CONTROL WIRING

Field wiring to the unit must conform to provisions of the current N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances. The unit must be electrically grounded in accordance with local codes or, in their absence, with the N.E.C./C.E.C. Voltage toler- ances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 3.

Electrical line must be sized properly to carry the load. Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused.

Refer to Figure 2 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information.

The wiring entering the cabinet must be provided with me- chanical strain relief.

A fused or HACR breaker disconnect switch should be field pro- vided for the unit. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wir- ing diagram.

COMPRESSORS

Units are shipped with compressor mountings factory-adjusted for shipping. CAUTION: Loosen compressor mounting bolts half turn before operating unit.

 

 

CONTROL WIRING

THERMOSTAT

UNIT TERMINAL STRIP

** = Minimum wire size of 18 AWG

R

**

R

 

 

 

wire should be used for all field

 

 

 

installed 24 volt wire.

G

 

G

NOTE:

HEAT ANTICIPATOR SHOULD BE SET AT 0.25 AMPS FOR ALL MODELS.

PROGRAMMABLE

THERMOSTAT ONLY

*= Only required on units with supplemental electric heat.

YY

W * W

CC

24 VOLT TRANSFORMER

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCON- NECT SWITCH, WIRING & OVERCURRENT PROTECTION.

POWER WIRING

REFER TO ELECTRICAL DATA

TABLES TO SIZE THE DISCON-

NECT SWITCH, WIRING &

OVERCURRENT PROTECTION.

FIG. 2 - TYPICAL FIELD WIRING DIAGRAM

4

Unitary Products Group

Page 4
Image 4
York D1EB018 THRU 060 Power And Control Wiring, Compressors, Typical Field Wiring Diagram, Power Wiring

FAQ

What are the voltage tolerances for the compressor terminals?

The voltage tolerances for the compressor terminals are indicated on the unit Rating Plate and Table 3.

What wire size should be used for all field installed 24-volt wire?

The minimum wire size of 18 AWG should be used for all field installed 24-volt wire.

How should the heat anticipator be set for all models?

The heat anticipator should be set at 0.25 amps for all models.