036-21216-003-A-0204

TABLE 11: SUPPLY AIR BLOWER PERFORMANCE DHE/DHG0601 (5 TON GAS HEAT MODELS)

UNIT

AIR FLOW

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE - IWG2

 

 

 

 

 

 

SIZE

CFM

 

0.20

 

0.30

 

0.40

 

0.50

 

0.60

 

0.70

 

0.80

(MBH)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

 

Watts

RPM

 

Watts

RPM

 

Watts

RPM

 

Watts

RPM

 

Watts

RPM

 

Watts

RPM

 

Watts

 

 

 

 

 

 

 

 

 

 

 

2500

 

1059

 

1560

1077

 

1590

1095

 

1630

1114

 

1650

1134

 

1660

1158

 

1685

1181

 

1720

 

2400

 

1032

 

1405

1054

 

1470

1074

 

1525

1094

 

1560

1116

 

1595

1140

 

1620

1167

 

1640

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2300

 

1005

 

1260

1024

 

1275

1049

 

1370

1069

 

1440

1090

 

1475

1116

 

1505

1142

 

1535

 

2200

 

980

 

1160

1002

 

1170

1022

 

1190

1044

 

1250

1066

 

1350

1090

 

1410

1117

 

1440

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2100

 

930

 

1060

957

 

1070

983

 

1080

1010

 

1100

1039

 

1160

1064

 

1260

1092

 

1340

060

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2000

 

877

 

950

908

 

975

941

 

1000

976

 

1020

1009

 

1050

1040

 

1100

1070

 

1225

 

1900

 

-

 

-

-

 

-

894

 

885

940

 

940

980

 

980

1014

 

1020

1047

 

1095

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1800

 

-

 

-

-

 

-

855

 

815

903

 

860

950

 

905

988

 

940

1022

 

970

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1700

 

-

 

-

-

 

-

-

 

-

884

 

815

925

 

850

964

 

880

1001

 

910

 

1600

 

-

 

-

-

 

-

-

 

-

864

 

770

908

 

805

948

 

835

987

 

870

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1500

 

-

 

-

-

 

-

-

 

-

-

 

-

882

 

740

926

 

780

965

 

830

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

AIR FLOW

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE IWG1

 

 

 

 

 

 

SIZE

CFM

 

0.90

 

1.00

 

1.10

 

1.20

 

1.30

 

1.40

 

1.50

(MBH)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

 

Watts

RPM

 

Watts

RPM

 

Watts

RPM

 

Watts

RPM

 

Watts

RPM

 

Watts

RPM

 

Watts

 

 

 

 

 

 

 

 

 

 

 

2500

 

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

 

2400

 

1193

 

1665

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2300

 

1170

 

1580

1202

 

1620

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2200

 

1148

 

1480

1180

 

1530

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

 

2100

 

1121

 

1385

1155

 

1425

1190

 

1475

-

 

-

-

 

-

-

 

-

-

 

-

060

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2000

 

1100

 

1285

1133

 

1340

1169

 

1385

1205

 

1445

-

 

-

-

 

-

-

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1900

 

1079

 

1180

1110

 

1240

1143

 

1280

1178

 

1330

1222

 

1375

-

 

-

-

 

-

 

1800

 

1058

 

1060

1090

 

1135

1122

 

1190

1158

 

1240

1196

 

1295

-

 

-

-

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1700

 

1035

 

960

1071

 

1030

1103

 

1100

1134

 

1140

1164

 

1175

1197

 

1205

-

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1600

 

1020

 

900

1056

 

965

1088

 

1035

1118

 

1065

1145

 

1105

1170

 

1130

1198

 

1150

 

1500

 

1004

 

860

1038

 

880

1070

 

925

1101

 

980

1130

 

1045

1158

 

1075

1184

 

1110

1.Models shown at 230/460 Volts with side duct connections.

2.Includes allowances for a wet evaporator coil, 1” filters and the heat exchangers. Refer to Table 12 for resistance values on appli- cations other than gas / electric units with side duct airflows.

TABLE 12: ACCESSORY STATIC RESISTANCE

 

 

 

 

 

EXTERNAL STATIC PRESSURE DROP

 

 

 

DESCRIPTION

 

 

 

 

RESISTANCE, IWG

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

1200

1400

1600

1800

2000

2200

2400

2600

2800

3000

ECONMIZER1 2

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

0.30

ELECTRIC

5-15 kW

0.04

0.05

0.06

0.07

0.08

0.10

0.12

0.14

0.16

0.19

0.22

HEATERS3

20 - 30 kW

0.06

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

BOTTOM DUCT

CONNECTIONS1

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

0.19

0.22

COOLING ONLY2

0.08

0.10

0.12

0.14

0.16

0.18

0.20

0.23

0.26

0.29

0.32

1.Deduct these resistance values from the available external static pressure shown in Tables 10 and 11.

2.The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

3.Add these resistance values to the available static resistance values on Tables 10 and 11.

Unitary Products Group

13

Page 13
Image 13
York D1HE/D1HG036, D2HE/D2HG060 warranty Accessory Static Resistance