036-21216-003-A-0204

TABLE 2: CAPACITY RATINGS - COOLING / GAS HEATING

 

 

 

ARI RATINGS1

 

 

 

 

GAS HEAT CAPACITY

 

 

MODEL

COOLING CAPACITY

SOUND

INPUT

DOE

AFUE3

 

S.S.E.4

S.E.5

TEMP. RISE

GAS

 

°

 

 

 

 

 

 

80 / 67-95 F

 

RATING2

(MBH)

OUTPUT

(%)

 

(%)

(%)

(°F)

LINE SIZE

 

 

MBH

SEER6

 

EER7

(dBels)

(MBH)

 

(in. O.D.)

 

 

 

 

 

 

 

 

 

DHG036N040

42.5

12.25

 

11.1

86

50

40

80.0

 

81.6

77.3

15-45

1/2

DHG036N079

42.5

12.25

 

11.1

86

100

79

80.5

 

80.8

77.9

40-70

1/2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DHG048N060

46.5

13.20

 

11.40

87

75

59

80.9

 

81.6

77.3

25-55

1/2

 

 

 

 

 

 

 

 

 

 

 

DHG048N099

 

125

99

80.3

 

80.6

77.9

45-75

1/2

 

 

 

 

 

 

DHG060N079

57.0

12.20

 

10.60

86

100

79

80.5

 

80.8

73.6

25-55

1/2

 

 

 

 

 

 

 

 

 

 

 

DHG060N099

 

125

99

80.3

 

80.6

77.9

35-65

1/2

 

 

 

 

 

 

1.Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.

2.Rated in accordance with ARI Standard 110, utilization range “A”.

3.AFUE = Annual Fuel Utilization Efficiency - determined in accordance with DOE test procedure.

4.S.S.E. = Steady State Efficiency. (Percent Output)

5.S.E. = California Seasonal Efficiency - determined in accordance with test procedures as specified by the State of California Energy Commission. Furnaces are available with a low NOx accessory.

6.SEER = Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.

7.EER = Energy Efficiency Ratio - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts at any given set of rating conditions, expressed in BTUH per watt (BTUH/watt).

TABLE 3: SOUND POWER RATINGS1

UNIT

 

ESP

BLOWER

 

 

 

 

SOUND POWER (dB 10-12Watts)

 

 

SIZE

CFM

 

 

 

 

OCTAVE BAND CENTERLINE FREQUENCY (Hz)

 

SWL

dBA

 

 

IWG

SPEED

kW

63

125

250

500

1000

2000

4000

8000

dB(A)

@ 10 ft.2

036

1200

0.60

LOW

0.60

84

84

74

67

69

62

57

52

74

41

048

1600

0.55

HIGH

0.80

85

85

75

68

70

63

58

53

75

42

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

2000

0.45

HIGH

1.00

86

86

76

69

71

64

59

54

76

43

1.These values have been accessed using a model of sound propagation from a point source into the hermispheric free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacturer has no way of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.

2.At a distance of 10 feet from the blower.

TABLE 4: PHYSICAL DATA - BASIC UNIT

 

MODELS

 

 

DHE/DHG

 

 

 

 

036

048

060

EVAPORATOR

CENTRIGUGAL BLOWER (Dia. x Wd. in.)

12 x 10

12 x 10

12 x 10

1.5

BLOWER

FAN MOTOR HP (BELT-DRIVE)

1.5

1.5

 

 

 

 

 

 

EVAPORATOR

ROWS DEEP

4

4

4

FINS PER INCH

13

13

13

COIL

FACE AREA (Sq. Ft.)

4.3

5.1

5.1

 

 

 

 

 

 

CONDENSER

PROPELLER DIA. (in.)

24

24

24

FAN MOTOR HP

1/2

1/2

1/2

FAN

NOM. CFM TOTAL

4,500

4,200

4,200

 

 

 

 

 

 

AIR

QUANITY PER UNIT (15” X 20” X 1”)

2

2

2

QUANTITY PER UNIT (14” X 25” X 1”)

1

1

1

FILTERS1

TOTAL FACE AREA (square feet)

6.6

6.6

6.6

 

SYSTEM

REFRIGERANT 22 (pounds/ounces)

10/8

10/*4

10/14

CHARGE

 

 

 

 

 

COMPRESSOR

QUANTITY PER UNIT (Hermetic Type)

1 / Recpt.

1 / Recpt.

1/Recpt.

1.Filter racks are adapted for 1” or 2” thick filters.

6

Unitary Products Group

Page 6
Image 6
York D2HE/D2HG060, D1HE/D1HG036 Capacity Ratings Cooling / GAS Heating, Sound Power RATINGS1, Physical Data Basic Unit