036-21216-003-A-0204

TABLE 18: ELECTRICAL DATA - COOLING/ELECTRIC HEAT DHE060

 

 

 

HEATER

SUPPLY

 

ELECTRIC HEATERS

TOTAL

MAX.

MAX.

 

 

 

AIR

 

 

 

 

MODEL

POWER

ACCESSORY

 

 

 

 

UNIT

FUSE

SIZE

BLOWER

 

 

 

TOTAL

DHE

SUPPLY

MODEL

kW

 

STAGES

AMPACITY

SIZE1

HACR2

MOTOR

 

 

 

 

NUMBER

 

 

 

AMPS

AMPS

AMPS

AMPS

 

 

 

FLA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2CE045005253

 

4.0

 

1

11.0

26.0

40

40

 

 

 

2CE045007254

 

5.6

 

1

15.6

26.9

40

40

 

 

208-3-60

2CE04501025

6.0

8.0

 

1

22.1

35.1

40

40

 

 

2CE04501525

11.9

 

2

33.1

48.9

50

50

 

 

 

 

 

 

 

 

2CE04502025

 

15.9

 

2

44.2

62.7

70

70

 

 

 

2CE04503025

 

22.2

 

2

61.7

84.6

90

90

 

 

 

2CE045005254

 

5.3

 

1

12.7

26.0

40

40

 

 

 

2CE045007254

 

7.5

 

1

18.0

30.1

40

40

060

 

230-3-60

2CE04501025

6.0

10.6

 

1

25.5

39.4

40

40

 

 

 

2CE04501525

 

15.9

 

2

38.2

55.3

60

60

 

 

 

2CE04502025

 

21.2

 

2

51.0

71.2

80

80

 

 

 

2CE04503025

 

29.6

 

2

71.2

96.5

100

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2CE045007464

 

6.8

 

1

8.2

14.0

20

20

 

 

 

2CE045010464

 

10.1

 

1

12.1

18.9

20

20

 

 

460-3-60

2CE045015464

3.0

13.6

 

1

16.4

24.2

25

25

 

 

 

2CE045020464

 

19.5

 

2

23.5

33.1

35

35

 

 

 

2CE045030464

 

28.8

 

2

34.6

47.1

50

50

1.Dual element, time delay type.

2.Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.

3.These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago), refer to Table 17 for fuse block accessories available for field installation.

FIGURE 2 - FIELD POWER WIRING

COOLINGONLY(24VOLTTHERMOSTAT)

THERMOSTAT1 UNITTERMINAL

TERMINALS STRIPTB1

RVR

 

 

24VOLT

YC

Y1

TRANSFORMER

 

 

 

Y2

 

GF

B

124VOLTTHERMOSTAT2TH07701024IFTHEUNITHASANECONOMIZER, REMOVEJUMPERJ1FROMTERMINALS8AND10ONTHERELAYBOARD TOPREVENTSIMULTANEOUSOPERATIONOFTHECOMPRESSORAND THEECONOMIZER.IFYOUWANTTOCONTROLTHEECONOMIZERONA SECONDSTAGEOFCOOLING,USETHETHERMOSTAT2TH04701224.

FIGURE 3 - CONTROL WIRING COOLING ONLY

16

Unitary Products Group

Page 16
Image 16
York D2HE/D2HG060, D1HE/D1HG036 warranty Electrical Data COOLING/ELECTRIC Heat DHE060, Amps FLA