troubleshooting without affecting the normal system operat- ing pressures.
AIR FILTERS - Units are shipped with 1" throwaway filters. The unit filter racks can accommodate 1" or 2" filters without any modifications
FACTORY-INSTALLED OPTION
ECONOMIZERS: Units equipped with a
The single enthalpy system contains a sensor that monitors the outdoor air which automatically operates the damper actuator allowing the dampers to open or close.
The dual enthalpy system contains a second sensor that monitors both the temperature and the humidity of the return air in addition to the outdoor air sensor described for a single enthalpy system. The logic module compares the inputs from both sensors and switches to economizer operation when- ever the outdoor air is cooler than the return air for maximum efficiency of the economizer system.
The economizer is completely wired and installed at the fac- tory. Only the outdoor air hood, including its filters, need be assembled and installed in the field.
FIELD-INSTALLED ACCESSORIES
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZER - Includes a
DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZER - Includes the same damper system and rain hood with filters as described for a single enthalpy economizer except this accessory contains two enthalpy sensors. It uses a differen- tial enthalpy control that compares the outdoor air versus the return air. The logic module then optimizes the economizer operation for additional savings over the single input econo- mizer.
MOTORIZED AIR DAMPER - Includes a
MANUAL OUTDOOR DAMPER - Provides 0% through 35% or 0% through 100% of return air opening (field adjustable). Designed for duct mounted side or bottom supply/return applications. Includes rain hood assembly and filter.
ELECTRIC HEATERS - Include nickel chromium elements, a terminal block, fuses (where required by UL), all the neces- sary connectors and hardware. All heaters utilize single point power supply hookup. Capacities from 5 KW thru 30 KW heating are available.
FUSE BLOCK KITS - These kits have a fuse box with a fuse block and fuses. They're available for all
OUTDOOR THERMOSTAT - A
ROOF CURB - This 14" high full perimeter roof curb is shipped knocked down for field assembly and contains duct supports that can easily be
shifted for the desired unit duct arrangement. No insulated deck is required because the unit underside is insulated.
START ASSIST KIT - Provides increased starting torque for single phase units in areas with low voltage conditions. It con- tains a 12.5 OHM PTCR temperature resistor with a support clip and hardware for mounting.
LOW AMBIENT KIT - A head pressure controller maintains stable system operation by reducing the speed of the con- denser fan motor when the outdoor temperature is between 45 and 0F. Condenser fan motors with ball bearings and heavier windings are also available for these low ambient applications.
PROPANE CONVERSION KIT - Converts a
LOW NOx KIT (natural gas furnaces only) - Contains five stainless steel expanded metal sheets for mounting into the heat exchanger tubes to meet the California low nitrous oxide emission requirements.
HIGH ALTITUDE CONVERSION (NATURAL AND PRO- PANE) - Provides orifices for proper furnace operation at alti- tudes up to 6000 feet. For propane applications, the propane conversion kit will also be required.
GAS PIPING - This kit contains 1/2" pipe nipples, fittings and gas cock (including panel access gaskets) required for bot- tom gas supply connection with external
OUTDOOR COIL GUARD - Consists of
4 | Unitary Products Group |