York D1HE/D1HG036, D2HE/D2HG060 warranty Unit Dimensions Dhg Unit, Clearances, 036-21216-003-A-0204

Models: D1HE/D1HG036 D2HE/D2HG060

1 28
Download 28 pages 3.44 Kb
Page 19
Image 19
FIGURE 9 - UNIT DIMENSIONS DHG UNIT

036-21216-003-A-0204

FIGURE 9 - UNIT DIMENSIONS DHG UNIT

TABLE 20: CLEARANCES

FRONT

 

DHE UNITS

24”

 

DHG UNITS

32”

 

 

 

 

 

 

 

 

 

12” (Less Economizer)

BACK

 

36” (With Economizer or

 

Fixed Air/Motorized

 

 

 

 

 

 

Damper)

 

 

 

 

LEFT SIDE (Filter Access)

 

24” (Less Economizer)

 

36” (With Economizer)

 

 

 

 

 

 

RIGHT SIDE (Cond. Coil)

 

24”

BELOW UNIT1

 

0”

ABOVE UNIT2

 

72” (For Condenser Air

 

Discharge)

 

 

 

1.Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.

2.Units must be installed outdoors. Overhanging struc- tures or shrubs should not obstruct condenser air dis- charge outlet.

RETURNAIR

TABLE 20: CLEARANCES SUPPLYAIR

OUTDOORAIR

OUTDOORAIR (Economizer)

All dimensions are in inches. They are subject to change without notice. Certi- fied dimensions will be provided upon request.

NOTE: DHG modes must be provided a 1” clearance between any combustible material and the supply air ductwork for a distance of 2 feet from the unit.

The products of combustion must not be allowed to accumu- late with a confined space and recirculate. Locate unit so that the vent air outlet hood is at least.

Three feet above any forced air inlet located within 10 horizontal feet (excluding those integral to the unit).

Four feet below, 4 horizontal feet from, or 1 foot above any door or gravity air inlet into the building.

Four feet from electric meters, gas meters, regulators and relief equipment.