035-14832-003-A-0204

TABLE 8 - STATIC RESISTANCES

EXTERNAL STATIC PRESSURE DROP

 

 

 

 

RESISTANCE, IWG

 

 

 

DESCRIPTION

 

 

 

 

CFM

 

 

 

 

 

1000

1200

1400

1600

1800

2000

2200

2400

2600

Economizer1, 2

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

Bottom Duct Connections1

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

1Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

2The pressure thru the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

TABLE 9 - MOTOR AND DRIVE DATA - Belt-Drive Blower

 

 

 

MOTOR*

 

ADJUSTABLE

 

FIXED

BELT

 

BLOWER

 

 

MOTOR PULLEY

BLOWER PULLEY

 

 

 

 

 

 

 

MODEL

RANGE

 

 

FRAME

SERVICE

PITCH

BORE

PITCH

BORE

PITCH

DESIG-

 

(RPM)

HP

RPM

DIA.

DIA.

 

LENGTH

 

SIZE

FACTOR

(in.)

 

(in.)

NATION

 

 

 

 

(in.)

(in.)

 

(in.)

 

 

 

 

 

 

 

 

 

 

DEG 036

790 - 1120

1-1/2

1725

56

1.15

2.4 - 3.4

7/8

3.7

 

1

37.3

A36

DEG 048

790 - 1120

1-1/2

1725

56

1.15

2.4 - 3.4

7/8

5.7

 

1

37.3

A36

DEG 060

850 - 1220

1-1/2

1725

56

1.15

2.4 - 3.4

7/8

5.2

 

1

37.3

A36

*All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device.

TABLE 10 - ELECTRICAL DATA - w/Direct-DriveBlower Motor

 

 

VOLTAGE

 

 

COND.

SUPPLY

 

MAX.

MAX.

 

 

LIMITATIONS

COMPRESSOR

AIR

MINIMUM

FUSE

HACR

MODEL

POWER

FAN

(SEE NOTE 1)

 

 

BLOWER

CIRCUIT

SIZE,

BREAKER

DEG

SUPPLY

 

 

MOTOR,

 

 

 

 

MOTOR,

AMPACITY

(SEE NOTE 2)

SIZE,

 

 

MIN.

MAX.

RLA

LRA

FLA

 

 

FLA

 

AMPS

AMPS

 

 

 

 

 

 

 

 

 

208/230-1-60

187

253

16.7

87

2.3

4.4

27.5

40

40

036

208/230-3-60

187

253

13.1

110

2.3

4.4

23.1

35

35

460-3-60

414

504

6.7

54

1.4

2.0

12.0

15

15

 

 

575-3-60

518

630

5.1

44

1.4

2.2

10.7

15

15

 

208/230-1-60

187

253

18.7

135

2.3

5.0

38.6

60

60

048

208/230-3-60

187

253

11.9

130

2.3

5.0

25.7

40

40

460-3-60

414

504

6.3

64

1.4

2.2

13.2

20

20

 

 

575-3-60

518

630

4.9

52.0

1.4

2.2

11.4

15

15

 

208/230-1-60

187

253

32.1

135

2.3

6.6

49.0

80

80

060

208/230-3-60

187

253

19.3

150

2.3

6.6

33.0

50

50

460-3-60

414

504

10.0

73

1.4

3.3

17.2

25

25

 

 

575-3-60

518

630

7.9

50

1.4

3.3

14.6

20

20

NOTES: 1. Utilization Range “A” in accordance with ARI Standard 110.

2. Dual element, time delay type.

 

 

 

TABLE 11 - ELECTRICAL DATA - w/Belt-DriveBlower Motor

 

 

VOLTAGE

 

 

COND.

SUPPLY

 

MAX.

MAX.

 

 

LIMITATIONS

COMPRESSOR

AIR

MINIMUM

FUSE

HACR

MODEL

POWER

FAN

(SEE NOTE 1)

 

 

BLOWER

CIRCUIT

SIZE,

BREAKER

DEG

SUPPLY

 

 

MOTOR,

 

 

 

 

MOTOR,

AMPACITY

(SEE NOTE 2)

SIZE,

 

 

MIN.

MAX.

RLA

LRA

FLA

 

 

FLA

 

AMPS

AMPS

 

 

 

 

 

 

 

 

 

208/230-1-60

187

253

16.7

87

2.3

7.6

30.7

45

45

036

208/230-3-60

187

253

13.1

110

2.3

5.3

23.9

35

35

460-3-60

414

504

6.7

54

1.4

2.6

12.4

20

20

 

 

575-3-60

518

630

5.1

44

1.4

2.0

9.8

15

15

 

208/230-1-60

187

253

18.7

135.0

2.3

8.6

42.6

60

60

048

208/230-3-60

187

253

11.9

130.0

2.3

5.2

26.3

40

40

460-3-60

414

504

6.3

64.8

1.4

2.6

14.3

20

20

 

 

575-3-60

518

630

4.9

52.0

1.4

2.0

11.4

15

15

 

208/230-1-60

187

253

32.1

169

2.3

8.6

51.0

80

80

060

208/230-3-60

187

253

19.3

123

2.3

6.0

32.4

50

50

460-3-60

414

504

10.0

62

1.4

3.0

16.9

25

25

 

 

575-3-60

518

630

7.9

50

1.4

2.4

13.7

20

20

NOTES: 1. Utilization Range “A” in accordance with ARI Standard 110.

2. Dual element, time delay type.

 

 

 

Unitary Products Group

11

Page 11
Image 11
York D2EG 048 Static Resistances, Blower Circuit Size Breaker DEG Supply Motor Ampacity, Min Max Rla Lra, FLA Amps