RETURN AIR REQUIREMENTS
CLOSET INSTALLATIONS
Additional Requirements
Additional requirements for floor and ceiling return system for closet installed sealed combustion heating appliance are given in the next paragraph.
Floor or Ceiling Return Air System
Listed in the next paragraph are the conditions to be met by Manufactured Home Manufacturers to have U.L. acceptance of
1.The
2.If the
3.The
4.The total free area of openings in the floor or ceiling reg- isters serving the
5.Materials located in the return duct system have a flame spread classification of 200 or less.
6.
7.Wiring materials located in the return duct system con- form to Article
8.Gas piping is not run in or through the return duct sys- tem.
9.The negative pressure in the closet as determined by test with the
speed and the closet door closed is to be not more nega- tive than minus
10.For floor return systems, the manufactured home manu- facturer or installer shall affix a prominent marking on or near the appliance where it is easily read when the ctoset door is open. The marking shall read:
_WARNING
HAZARD OF ASPHYXIATION, DO NOT COVER OR RESTRICT FLOOR OPENING
AIR DISTRIBUTION SYSTEMS
For proper air distribution, the supply duct system shall be designed so that the static pressure does not exceed the listed static pressure rating on the furnace rating plate.
Three typicaldistdbution systems are illustrated in Figure 2.
Location, size and number of registers should be selected on the basis of best air distribution and floor plan of the home.
The Air Temperature Rise is to be adjusted to obtain a tem- perature dse within the range(s) specified on the furnace rat- ing plate.
A |
|
Singletrunk duct _ | C |
E |
| TransitionDuct withBranches |
| B* | |
| Transitionduct | |
| Dualtrunk duct with crossoverconnector | |
|
|
Dualtrunk duct
Crossover
I
1.CrossoverDuct must becentereddirectlyunder furnace.
2.Use 12" DiameterRound or
3.
4.Flex_uct matedalmust be
FIGURE 2 : Air Distribution Systems
4 | Unitary Products Group |