| LOCATOR BRACKET |
| |
|
| NAILS, FLAT HEAD SCREWS | |
|
| OR STAPLES | |
_ | NAI L_,AFLEATHEAD SC R EWS | BEND TABS UNDER | |
OPENING TO | |||
|
| ||
|
| SECURE TO THE | |
| FLOOR | SUPPLY DUCT | |
|
|
SUPPLY DUCT
FIGURE tl : Duct Connector Screw Attachment
INSTALLATION OF SCREW A'B'ACHMENTDUCT
CONNECTOR
1, Make floor cut out as shown in Figure 9.
2.Determine the depth of the floor cavity from the surface of the floor to the top of the supply air duct and select the appropriate duct connector from the chart.
3.Place locating bracket (supplied with the duct connector) to the back edge of the floor opening. See Figure 11.
4.Apply a water based duct sealant to the 1/2" supply duct attachment flange of the duct connector.
5.Determine which of the four positions the duct connector
best centers over the supply duct and insert it through the floor cutout.
6.When propedy aligned with the supply duct, secure the duct connector to the floor with nails, flat head screws or staples.
7.Use screws as required to secure the duct connector to the supply duct.
8.Cut out the opening to the supply duct. If sealant was not used, the instaner should tape the mating flanges to pro- vide s good air seal.
NOTE: Duct sealant and tape must be classified as meeting HUD Standard 3280.715, U.L. Standard 181A.
If tape is used to provide a better air seal, it should be a type approved by the applicable national or local codes.
SUPPLY DUCT
FIGURE t2 : Duct Connector Tab Attachment
INSTALLATION OF TAB ATTACHMENT DUCT
CONNECTORS
1.Make floor cut out as shown in Figure 9.
2.Determine the depth of the floor cavity from the surface of the floor to the top of the supply air duct and select the appropriate duct connector from the chart.
3.Place locating bracket (supplied with the duct connector)
to the rear of the floor area for the furnace. See Figure
12.
4.Determine which of the four positions the duct connector
best centers over the supply duct and insert it through the floor cutout.
5.Mark
6.Cut out the opening to the supply duct.
7.Bend tabs down through and back up under the supply duct.
8.Secure the duct connector to the floor with nails, flat head screws or staples.
The duct connector is designed for use on ducts down to 12" in width. When using the connector on smaller width ducts, there will not be sufficientclearance to bend the tabs on two sides of the duct connector.
In such cases the tabs may be attached to the sides of the duct by using sheet metal screws or other suitable fasteners. Holes for sheet metal screws are provided in three (3) tabs on each side of the duct connector. If more than 3 tabs need to be used to provide a more secure and air tight connection, the remaining tabs can also be fastened to the duct with screws after drilling the required screw holes.
10 | Unitary Products Group |