York DJ 180 warranty Minimum Clearances

Models: DJ 180

1 40
Download 40 pages 57.41 Kb
Page 32
Image 32
TABLE 26: MINIMUM CLEARANCES

TABLE 26: MINIMUM CLEARANCES

LOCATION

CLEARANCE

Front

36”

Rear

24” (Less Economizer)

49” (With Economizer)

 

 

 

Left Side (Filter Access)

24” (Less Economizer)

36” (With Economizer)3

Right Side (Cond. Coil)

36”

Below Unit1

0”

Above Unit2

72” With 36” Maximum

Horizontal Overhang (For

 

Condenser Air Discharge)

1.Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.

2.Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.

3.If economizer is factory installed, the unassembled rain hood must be removed from its ride along position in front of evapora- tor coil, or in the outdoor air compartment, prior to final installa- tion.

261660-YTG-C-0707

NOTE: ELEC / ELEC Models: Units and ductwork are approved for zero clearance to combustible material when equipped with electric heaters.

GAS / ELEC Models: A 1” clearance must be provided between any combustible material and the supply air ductwork for a distance of 3 feet from the unit.

The products of combustion must not be allowed to accumulate within a confined space and recirculate.

Locate unit so that the vent air outlet hood is at least:

Three (3) feet above any force air inlet located within 10 horizontal feet (excluding those integral to the unit).

Four (4) feet below, four horizontal feet from, or one foot above any door or gravity air inlet into the building.

Four (4) feet from electric and gas meters, regulators and relief equipment.

 

 

ECONOMIZER

 

 

 

 

MOTORIZED

 

 

SUPPLY AIR

POWER EXHAUST

DAMPER

 

 

RAIN HOOD

RAIN HOOD

 

 

COMPARTMENT

ECONOMIZER / MOTORIZED DAMPER

 

(on Return Air Compartment)

(on Outdoor Air Compartment)

 

 

 

 

AND POWER EXHAUST RAIN HOODS

 

 

 

 

 

 

 

 

FIXED

 

 

 

 

OUTDOOR AIR

 

 

 

 

INTAKE HOOD

 

 

 

 

(located on

 

 

 

 

Return Air

 

 

 

36-5/8”

Compartment)

 

 

 

 

 

 

 

 

 

1“ CONDENSATE

 

 

 

16-1/8”

DRAIN

 

 

 

 

(Must be trapped)

 

 

5”

 

 

 

 

 

28-3/16”

92”

 

REAR VIEW

 

 

LH VIEW

DETAIL “Y”

UNIT WITH RAIN HOODS

FIGURE 6 - UNIT DIMENSIONS DJ180, 210, 240 & 300 (RAINHOOD)

32

Unitary Products Group

Page 32
Image 32
York DJ 180 warranty Minimum Clearances