York DJ 180 warranty Volt And Standard Drive, Volt And High Static Drive, 230/460/575

Models: DJ 180

1 40
Download 40 pages 57.41 Kb
Page 19
Image 19

261660-YTG-C-0707

TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - GAS HEAT 180 MBH - BOTTOM DUCT CONNECTIONS

BLOWER

MOTOR

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

PULLEY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPEED,

 

 

4500

 

 

 

5250

 

 

6000

 

 

6750

 

 

7200

 

(TURNS

 

 

 

 

 

 

 

 

 

 

 

 

(RPM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPEN)*

ESP

 

BHP

 

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208 VOLT AND STANDARD DRIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

850

6.0**

0.9

 

2.4

 

2.1

0.6

2.9

2.6

0.3

3.4

3.0

-

-

-

-

-

-

870

5.5

1.0

 

2.5

 

2.2

0.7

3.0

2.7

0.4

3.5

3.1

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

915

4.5

1.1

 

2.6

 

2.4

0.8

3.1

2.8

0.5

3.6

3.2

0.2

4.1

3.7

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

965

3.5

1.2

 

2.7

 

2.5

0.9

3.2

2.9

0.6

3.7

3.3

0.4

4.4

3.0

0.2

5.0

4.5

980

3.0

1.3

 

2.9

 

2.6

1.0

3.4

3.0

0.7

3.8

3.4

0.5

4.5

4.0

0.3

5.1

4.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1010

2.0

1.4

 

3.0

 

2.7

1.1

3.6

3.2

0.8

4.0

3.6

0.6

4.7

4.2

0.4

5.4

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1040

1.0

1.6

 

3.2

 

2.9

1.3

3.8

3.4

1.0

4.4

3.9

0.8

5.0

4.5

0.6

5.6

5.0

208 VOLT AND HIGH STATIC DRIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

965

6.0

1.2

 

2.7

 

2.5

0.9

3.2

2.9

0.6

3.7

3.3

0.4

4.4

3.9

0.2

5.0

4.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

980

5.5

1.3

 

2.9

 

2.6

1.0

3.4

3.0

0.7

3.8

3.4

0.5

4.5

4.0

0.3

5.1

4.6

1025

4.5

1.4

 

3.1

 

2.8

1.2

3.6

3.2

0.9

4.1

3.7

0.7

4.8

4.3

0.4

5.5

4.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1065

3.5

1.6

 

3.4

 

3.0

1.4

3.9

3.5

1.1

4.5

4.0

0.9

5.1

4.6

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1125

2.0

1.9

 

3.6

 

3.2

1.7

4.4

3.9

1.4

5.0

4.5

1.2

5.8

5.2

-

-

-

1170

1.0

2.1

 

3.9

 

3.5

1.9

4.7

4.2

1.6

5.5

4.9

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230/460/575

VOLT AND

STANDARD

DRIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

870

6.0**

1.0

 

2.5

 

2.2

0.7

3.0

2.7

0.4

3.5

3.1

-

-

-

-

-

-

915

5.0

1.1

 

2.6

 

2.4

0.8

3.1

2.8

0.5

3.6

3.2

0.2

4.1

3.7

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

965

4.0

1.2

 

2.7

 

2.5

0.9

3.2

2.9

0.6

3.7

3.3

0.4

4.4

3.9

0.2

5.0

4.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

980

3.5

1.3

 

2.9

 

2.6

1.0

3.4

3.0

0.7

3.8

3.4

0.5

4.5

4.0

0.3

5.1

4.6

1015

2.5

1.4

 

3.0

 

2.7

1.1

3.6

3.2

0.8

4.0

3.6

0.6

4.7

4.2

0.4

5.4

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1050

1.5

1.5

 

3.1

 

2.8

1.2

3.7

3.3

0.9

4.2

3.8

0.7

4.9

4.4

0.5

5.7

5.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1065

1.0

1.6

 

3.4

 

3.0

1.4

3.9

3.5

1.1

4.5

4.0

0.9

5.1

4.6

-

-

-

230/460/575

VOLT AND

HIGH STATIC DRIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

980

6.0

1.3

 

2.9

 

2.6

1.0

3.4

3.0

0.7

3.8

3.4

0.5

4.5

4.0

0.3

5.1

4.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1045

4.5

1.6

 

3.2

 

2.9

1.3

3.8

3.4

1.0

4.4

3.9

0.8

5.0

4.5

0.6

5.6

5.0

1065

4.0

1.7

 

3.4

 

3.0

1.4

3.9

3.5

1.1

4.5

4.0

0.9

5.1

4.6

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1125

2.5

1.9

 

3.6

 

3.2

1.7

4.4

3.9

1.4

5.0

4.5

1.2

5.8

5.2

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1170

1.5

2.1

 

3.9

 

3.5

1.8

4.7

4.2

1.6

5.5

4.9

-

-

-

-

-

-

1190

1.0

2.2

 

4.0

 

3.6

1.9

4.8

4.3

1.7

5.6

5.0

-

-

-

-

-

-

NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil. 2.Refer to the additional Static Resistances table.

ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.

*Do NOT close the pulley below 1 turn open.

**Factory setting.