TABLE 12: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
UNIT DESCRIPTION / MODEL |
|
|
| DY060 / 5 Ton |
|
|
| ||
CONFIGURATION |
|
|
| Horizontal Ducted Inlet |
|
|
| ||
Indoor Blower Speed (RPM) | 840 | 845 | 1166 | 1188 | |||||
Blower Static Pressure (IWG) | 0.2 | 0.6 | 0.3 | 1.3 | |||||
Airflow (CFM) | 1695 | 1100 | 2618 | 1323 | |||||
Blower Motor BHP | 0.67 | 0.50 | 1.51 | 0.80 | |||||
| ID Blower | Cooling | ID Blower | Cooling | ID Blower |
| Cooling | ID Blower | Cooling |
Octave Center Freq. | Operation2 | Operation2 |
| Operation2 | Operation2 | ||||
| Only (dB) | (dB) | Only (dB) | (dB) | Only (dB) |
| (dB) | Only (dB) | (dB) |
|
|
|
|
|
| ||||
63 | 77 | 84 | 77 | 84 | 81 |
| 85 | 79 | 84 |
125 | 71 | 71 | 72 | 73 | 74 |
| 75 | 71 | 72 |
250 | 57 | 58 | 55 | 56 | 66 |
| 66 | 60 | 61 |
500 | 53 | 53 | 51 | 51 | 60 |
| 60 | 55 | 55 |
1000 | 50 | 50 | 45 | 46 | 60 |
| 60 | 53 | 53 |
2000 | 49 | 49 | 43 | 44 | 58 |
| 58 | 50 | 50 |
4000 | 49 | 49 | 42 | 43 | 59 |
| 59 | 47 | 47 |
8000 | 49 | 49 | 48 | 48 | 54 |
| 54 | 47 | 47 |
1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2.Cooling Operation – ID blower, compressor and outdoor fan operating.
3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4.Test duct termination is flush with reverberation room wall.
5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 13: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL |
|
|
| DY060 / 5 Ton |
|
|
| |
CONFIGURATION |
|
| Horizontal Ducted Discharge |
|
| |||
Indoor Blower Speed (RPM) | 840 | 845 | 1166 | 1188 | ||||
Blower Static Pressure (IWG) | 0.2 | 0.6 | 0.3 | 1.3 | ||||
Airflow (CFM) | 1695 | 1100 | 2618 | 1323 | ||||
Blower Motor BHP | 0.67 | 0.50 | 1.51 | 0.80 | ||||
| ID Blower | Cooling | ID Blower | Cooling | ID Blower | Cooling | ID Blower | Cooling |
Octave Center Freq. | Operation2 | Operation2 | Operation2 | Operation2 | ||||
| Only (dB) | (dB) | Only (dB) | (dB) | Only (dB) | (dB) | Only (dB) | (dB) |
|
|
|
|
| ||||
63 | 82 | 87 | 79 | 88 | 88 | 89 | 82 | 87 |
125 | 75 | 76 | 72 | 74 | 82 | 83 | 78 | 78 |
250 | 69 | 69 | 66 | 66 | 79 | 79 | 73 | 73 |
500 | 64 | 64 | 60 | 60 | 72 | 72 | 66 | 66 |
1000 | 59 | 60 | 55 | 56 | 68 | 68 | 61 | 61 |
2000 | 55 | 55 | 50 | 50 | 65 | 65 | 57 | 57 |
4000 | 58 | 58 | 52 | 52 | 68 | 68 | 60 | 60 |
8000 | 55 | 55 | 49 | 49 | 66 | 67 | 56 | 56 |
1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2.Cooling Operation – ID blower, compressor and outdoor fan operating.
3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4.Test duct termination is flush with reverberation room wall.
5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Johnson Controls Unitary Products | 13 |