York DY 060 Unit Dimensions Rear View, Minimum Clearances, Hole, Opening Size Dia, Used For

Models: DY 048 DY 060

1 36
Download 36 pages 25.65 Kb
Page 28
Image 28
FIGURE 7 - UNIT DIMENSIONS (REAR VIEW)

343615-YTG-B-0308

FIGURE 7 - UNIT DIMENSIONS (REAR VIEW)

Filter Access

 

 

Blower Motor Access

 

 

Dot Plugs

 

 

Field-Supplied Disconnect

 

 

Switch Location

 

 

Mounting Bracket for

 

 

Disconnect Switch

A,B

 

(Field Supplied)

 

 

Wiring Entry

Control Box Access

 

(See Detail “B”)

Disconnect Switch Location and Motor Access Panel for Unit with “Belt-Drive” Option

FIGURE 8 - DISCONNECT/BLOWER ACCESS LOCATION TABLE 28: UTILITIES ENTRY

HOLE

OPENING SIZE (DIA.)

USED FOR

 

A

7/8” KO1

Control Wiring2

 

Side

 

Bottom

 

 

 

 

 

 

 

 

 

B

2” KO1

Power Wiring

 

Side

 

 

 

Bottom

 

 

 

 

 

 

 

 

C

1-5/8” KO

Gas Piping (Front)

D

1-1/2” KO

Gas Piping (Bottom)

 

 

 

 

 

1.Opening in the bottom to the unit can be located by the side in the insulation.

2.Do not remove the 2” knockout ring.

TABLE 29: MINIMUM CLEARANCES

LOCATION

CLEARANCE

Front

24” (Cooling/Electric Heat)

32” (Gas Heat)

 

 

 

Rear

12” (Less Economizer)

36” (With Economizer or Fixed

 

Air/Motorized Damper)

 

 

Left Side (Filter Access)

24” (Less Economizer)

36” (With Economizer)

 

 

 

Right Side (Cond. Coil)

24”

Below Unit1

0”

Above Unit2

72” (For

Condenser Air Discharge)

 

1.Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.

2.Units must be installed outdoors. Overhanging struc- tures or shrubs should not obstruct condenser air dis- charge outlet.

28