343615-YTG-B-0308

TABLE 19: SUPPLY AIR BLOWER PERFORMANCE (DY036, 048, & 060 DIRECT DRIVE) SIDE DUCT APPLICATION

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE - IWG2

 

 

 

 

 

 

 

UNIT

MOTOR1

0.2

 

0.3

 

0.4

 

0.5

 

0.6

 

0.7

 

0.8

 

0.9

 

1.0

 

TONNAGE

SPEED

CFM

 

WATTS

CFM

 

WATTS

CFM

 

WATTS

CFM

 

WATTS

CFM

 

WATTS

CFM

 

WATTS

CFM

 

WATTS

CFM

 

WATTS

CFM

 

WATTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HI

1582

 

320

1538

 

335

1496

 

349

1458

 

363

1418

 

376

1381

 

390

1338

 

403

1298

 

417

1255

 

430

 

MED/HI

1488

 

263

1440

 

276

1396

 

290

1354

 

303

1309

 

316

1263

 

329

1214

 

343

1158

 

358

1085

 

374

33

MED

1339

 

208

1292

 

221

1247

 

234

1201

 

246

1152

 

258

1102

 

272

1036

 

288

967

 

303

924

 

313

 

MED/LOW

1233

 

171

1184

 

183

1135

 

195

1082

 

207

1026

 

220

957

 

235

895

 

248

-

 

-

-

 

-

 

LOW

1081

 

130

997

 

134

935

 

145

863

 

158

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

 

HI

2056

 

636

2017

 

696

1978

 

714

1942

 

734

1906

 

749

1864

 

764

1815

 

769

1728

 

743

1582

 

685

 

MED/HI

1866

 

539

1832

 

557

1795

 

571

1754

 

585

1722

 

602

1679

 

619

1636

 

638

1582

 

653

1508

 

639

43

MED

1680

 

408

1641

 

426

1594

 

438

1558

 

455

1517

 

472

1469

 

490

1415

 

505

1370

 

521

1337

 

536

 

MED/LOW

1582

 

362

1541

 

380

1495

 

391

1465

 

406

1426

 

423

1377

 

440

1326

 

455

1292

 

469

1247

 

485

 

LOW

1300

 

223

1258

 

237

1202

 

247

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

 

HI

2256

 

883

2258

 

931

2247

 

950

2223

 

964

2182

 

979

2125

 

971

2044

 

940

1958

 

898

1864

 

854

 

MED/HI

2145

 

771

2127

 

784

2119

 

808

2089

 

826

2051

 

844

2014

 

859

1965

 

861

1896

 

843

1801

 

806

53

MED

2020

 

637

1999

 

656

1985

 

675

1947

 

696

1910

 

715

1876

 

730

1832

 

740

1793

 

756

1725

 

748

 

MED/LOW

1757

 

413

1713

 

432

1677

 

451

1639

 

468

1597

 

479

1559

 

497

1521

 

513

1472

 

523

-

 

-

 

LOW

1570

 

327

1536

 

339

1499

 

356

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

1.Factory set on medium speed tap.

2.Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values.

3.Side Duct application (230 Volts)

TABLE 20: SUPPLY AIR BLOWER PERFORMANCE (DY036, 048, & 060 DIRECT DRIVE) BOTTOM DUCT APPLICATION

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE - IWG2

 

 

 

 

 

 

 

UNIT

MOTOR1

0.2

 

0.3

 

0.4

 

0.5

 

0.6

 

0.7

 

0.8

 

0.9

 

1.0

 

TONNAGE

SPEED

CFM

 

WATTS

CFM

 

WATTS

CFM

 

WATTS

CFM

 

WATTS

CFM

 

WATTS

CFM

 

WATTS

CFM

 

WATTS

CFM

 

WATTS

CFM

 

WATTS

 

 

 

 

 

 

 

 

 

 

 

 

HI

1527

 

320

1485

 

335

1445

 

349

1408

 

363

1370

 

376

1334

 

390

1292

 

403

1254

 

417

1213

 

430

 

MED/HI

1437

 

263

1391

 

276

1349

 

290

1308

 

303

1265

 

316

1221

 

329

1174

 

343

1120

 

358

1049

 

374

33

MED

1293

 

208

1248

 

221

1205

 

234

1161

 

246

1114

 

258

1065

 

272

1002

 

288

935

 

303

894

 

313

 

MED/LOW

1191

 

171

1144

 

183

1097

 

195

1046

 

207

992

 

220

926

 

235

866

 

248

-

 

-

-

 

-

 

LOW

1045

 

130

964

 

134

904

 

145

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

 

HI

1985

 

636

1947

 

696

1909

 

714

1875

 

734

1840

 

749

1800

 

764

1752

 

769

1668

 

743

1528

 

685

 

MED/HI

1802

 

539

1768

 

557

1733

 

571

1694

 

585

1662

 

602

1621

 

619

1580

 

638

1528

 

653

1456

 

639

43

MED

1622

 

408

1585

 

426

1539

 

438

1505

 

455

1465

 

472

1419

 

490

1367

 

505

1324

 

521

1291

 

536

 

MED/LOW

1528

 

362

1489

 

380

1444

 

391

1415

 

406

1377

 

423

1330

 

440

1281

 

455

1248

 

469

1205

 

485

 

LOW

1256

 

223

1216

 

237

1161

 

247

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

 

HI

2177

 

883

2179

 

931

2169

 

950

2145

 

964

2106

 

979

2051

 

971

1973

 

940

1890

 

898

1800

 

854

 

MED/HI

2071

 

771

2053

 

784

2045

 

808

2016

 

826

1980

 

844

1944

 

859

1897

 

861

1830

 

843

1739

 

806

53

MED

1950

 

637

1929

 

656

1916

 

675

1880

 

696

1844

 

715

1811

 

730

1768

 

740

1731

 

756

1665

 

748

 

MED/LOW

1697

 

413

1654

 

432

1619

 

451

1583

 

468

1542

 

479

1506

 

497

1469

 

513

-

 

-

-

 

-

 

LOW

1516

 

327

1484

 

339

1448

 

356

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

-

 

-

1.Factory set on medium speed tap.

2.Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values.

3.Bottom Duct application (230 Volts)

18

Johnson Controls Unitary Products

Page 18
Image 18
York DY 060, DY 048 warranty Med