York DY 060 Unit Description / Model, DY060 / 5 Ton, Configuration, Vertical Ducted Discharge

Models: DY 048 DY 060

1 36
Download 36 pages 25.65 Kb
Page 14
Image 14
Vertical Ducted Inlet

 

 

 

 

 

 

 

 

343615-YTG-B-0308

TABLE 14: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT DESCRIPTION / MODEL

 

 

 

DY060 / 5 Ton

 

 

 

 

 

CONFIGURATION

 

 

 

Vertical Ducted Inlet

 

 

 

 

 

Indoor Blower Speed (RPM)

834

840

1171

1194

 

 

Blower Static Pressure (IWG)

0.2

0.6

0.2

1.3

 

 

Airflow (CFM)

1525

1019

2624

1256

 

 

Blower Motor BHP

0.61

0.44

1.43

0.83

 

 

 

ID Blower

Cooling

ID Blower

Cooling

ID Blower

Cooling

ID Blower

Cooling

 

 

Octave Center Freq.

Operation2

Operation2

Operation2

Operation2

 

 

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

(dB)

 

 

 

 

 

 

 

63

77

86

79

88

81

86

83

87

 

 

125

69

70

70

72

71

73

72

72

 

 

250

56

63

56

58

64

72

63

69

 

 

500

50

52

48

49

57

59

53

56

 

 

1000

48

51

44

45

57

58

49

52

 

 

2000

43

47

39

41

54

57

47

50

 

 

4000

47

49

40

41

55

61

47

52

 

 

8000

46

47

44

45

51

57

47

49

 

1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2.Cooling Operation – ID blower, compressor and outdoor fan operating.

3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

4.Test duct termination is flush with reverberation room wall.

5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

TABLE 15: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)

UNIT DESCRIPTION / MODEL

 

 

 

DY060 / 5 Ton

 

 

 

CONFIGURATION

 

 

Vertical Ducted Discharge

 

 

Indoor Blower Speed (RPM)

834

840

1171

1194

Blower Static Pressure (IWG)

0.2

0.6

0.2

1.3

Airflow (CFM)

1525

1019

2624

1256

Blower Motor BHP

0.61

0.44

1.43

0.83

 

ID Blower

Cooling

ID Blower

Cooling

ID Blower

Cooling

ID Blower

Cooling

Octave Center Freq.

Operation2

Operation2

Operation2

Operation2

 

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

(dB)

 

 

 

 

 

63

83

88

82

88

91

91

85

88

125

78

78

75

76

85

85

79

79

250

66

67

62

62

77

78

70

72

500

59

60

54

54

70

70

61

61

1000

57

58

51

51

68

68

57

58

2000

51

52

45

45

62

63

52

53

4000

54

54

47

47

65

66

55

56

8000

52

52

46

47

65

66

52

53

1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2.Cooling Operation – ID blower, compressor and outdoor fan operating.

3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

4.Test duct termination is flush with reverberation room wall.

5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

14

Johnson Controls Unitary Products

Page 14
Image 14
York DY 060 Unit Description / Model, DY060 / 5 Ton, Configuration, Vertical Ducted Discharge, Vertical Ducted Inlet