036-21020-003 Rev. C (0203)

COOLING PERFORMANCE

 

SUCT. T/P

 

AIR TEMP ON CONDENSER

 

 

SUCT. T/P

 

AIR TEMP ON CONDENSER

 

MODEL

@ COMPR.

75°F

95°F

115°F

MODEL

@ COMPR.

75°F

95°F

115°F

 

TEMP.

PSIG

MBH

KW

MBH

KW

MBH

 

KW

 

TEMP.

PSIG

MBH

 

KW

MBH

KW

MBH

KW

 

35

61.5

18.7

1.92

12.6

2.06

7.3

 

2.24

 

35

61.5

36.8

 

3.07

32.2

3.69

27.6

4.37

H4DH018S06

40

68.5

20.8

1.92

14.3

2.10

8.8

 

2.31

H4DH042S06

40

68.5

40.5

 

3.11

35.7

3.77

30.9

4.49

45

76.0

22.9

1.90

16.1

2.11

10.2

 

2.37

45

76.0

44.4

 

3.15

39.4

3.85

34.4

4.61

 

 

 

 

 

50

84.0

25.1

1.86

18.0

2.11

11.8

 

2.41

 

50

84.0

48.4

 

3.19

43.2

3.91

37.9

4.72

 

35

61.5

22.4

2.10

17.4

2.30

12.7

 

2.51

 

35

61.5

47.8

 

3.66

40.2

4.50

33.0

5.51

H4DH024S06

40

68.5

25.0

2.14

19.6

2.36

14.6

 

2.58

H4DH048S06

40

68.5

52.5

 

3.69

44.4

4.54

36.8

5.57

45

76.0

27.7

2.17

21.9

2.41

16.6

 

2.65

45

76.0

57.3

 

3.73

48.7

4.57

40.6

5.62

 

 

 

 

 

50

84.0

30.4

2.20

24.3

2.45

18.6

 

2.72

 

50

84.0

62.3

 

3.77

53.2

4.61

44.6

5.67

 

35

61.5

26.6

2.52

22.9

3.00

19.3

 

3.62

 

35

61.5

55.7

 

4.37

51.4

5.37

46.8

6.69

H4DH030S06

40

68.5

29.1

2.54

25.1

3.03

21.3

 

3.65

H4DH060S06

40

68.5

60.6

 

4.41

56.2

5.43

51.4

6.74

45

76.0

31.6

2.56

27.5

3.05

23.4

 

3.68

45

76.0

65.6

 

4.46

61.0

5.47

56.1

6.80

 

 

 

 

 

50

84.0

34.3

2.58

29.9

3.08

25.6

 

3.71

 

50

84.0

70.9

 

4.50

66.0

5.52

60.8

6.85

 

35

61.5

34.3

2.62

30.9

3.10

27.4

 

3.77

 

 

 

 

 

 

 

 

 

 

H4DH036S06

40

68.5

37.7

2.64

34.1

3.13

30.3

 

3.80

 

 

 

 

 

 

 

 

 

 

45

76.0

41.4

2.66

37.5

3.17

33.4

 

3.85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

84.0

45.1

2.69

41.0

3.21

36.7

 

3.90

 

 

 

 

 

 

 

 

 

 

1.For condensing unit only. Does not include effect of evaporator motor power or heat.

2.Performance based on 15° superheat and 15° sub-cooling at condensing unit.

a.Increase capacity 1% for each 2° increase in sub-cooling.

b.Decrease capacity 1% for each 2° decrease in sub-cooling.

3.Sub-cooling in excess of 20° may result in excessively high condensing temperature with air on condenser above 115°. Maximum recommended condensing temperature is 140°F.

ACCESSORIES

Refer to Price Manual for specific model numbers.

Hard Start Kit - Provides increased starting torque for areas with low voltage.

Compressor Blanket - Designed to further reduce the nor- mal compressor operating sound. Refer to price pages for specific match-ups.

Off Cycle Timer Delay - Provides a 5-minute off cycle to pre- vent rapid recycling of the compressor.

Room Thermostats - A wide selection of compatible thermo- sets are available to provide optimum performance and fea- tures for any installation.

1 Heat Stage only, manual, mechanical thermostat. Add sub- base for 1H/1C.

1H/1C, manual change-over electronic non-programmable thermostat.

1H/1C, auto/manual changeover, electronic programmable, deluxe 7-day, thermostat.

1H/1C, auto/manual changeover, electronic programmable.

*For the most current accessory information, refer to the price book or consult factory.

SOUND RATINGS

UNIT MODEL

SOUND RATINGS

DECIBELS*

 

 

 

018

70

 

 

024

72

 

 

030

72

 

 

036

74

 

 

042

76

 

 

048

76

 

 

060

76

 

 

*Rated in accordance with ARI Standard 270.