York H4DH018 THRU 060 warranty Cooling Performance Data, Air Conditioner Model No

Models: H4DH018 THRU 060

1 20
Download 20 pages 49.34 Kb
Page 15
Image 15
Manual background

036-21020-003 Rev. C (0203)

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

H4DH036S06

 

 

 

 

 

 

 

 

 

 

INDOOR COIL MODEL NO.

 

G1FA036S17,21

 

 

 

 

 

 

 

 

 

CONDENSER

ID CFM

 

1100

 

 

1200

 

 

1300

 

ENTERING AIR

ID DB

85

80

75

70

85

80

75

70

85

80

75

70

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

 

ID WB

72

67

62

57

72

67

62

57

72

67

62

57

 

T.C.

40.9

37.5

34.2

31.2

41.2

37.9

34.5

31.5

41.6

38.2

34.8

32.0

75

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

26.1

26.2

26.6

26.7

27.0

27.1

27.6

27.7

28.1

28.2

28.6

28.9

 

K.W

2.69

2.66

2.63

2.61

2.74

2.71

2.68

2.66

2.77

2.74

2.71

2.69

 

T.C.

39.7

36.4

33.2

30.3

40.1

36.7

33.5

30.6

40.3

37.1

33.7

31.0

85

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

25.6

25.8

26.1

26.2

26.7

26.7

27.1

27.2

27.5

27.7

28.0

28.4

 

K.W

2.91

2.87

2.84

2.81

2.96

2.92

2.88

2.86

2.99

2.95

2.92

2.89

 

T.C.

38.0

34.8

31.8

29.0

38.3

35.2

32.1

29.5

38.7

35.5

32.4

29.8

95

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

25.0

25.1

25.5

25.6

26.0

26.0

26.4

26.8

27.0

27.0

27.4

27.6

 

K.W

3.20

3.15

3.11

3.08

3.25

3.20

3.16

3.13

3.29

3.24

3.20

3.17

 

T.C.

36.4

33.4

30.4

27.7

36.7

33.7

30.6

28.2

36.8

33.9

30.9

28.5

105

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

24.5

24.5

24.8

24.8

25.5

25.5

25.7

26.0

26.3

26.5

26.8

27.0

 

K.W

3.54

3.49

3.44

3.40

3.59

3.54

3.49

3.45

3.63

3.58

3.53

3.49

 

T.C.

34.6

31.9

28.9

26.6

34.8

32.0

29.1

26.8

35.2

32.2

29.6

27.1

115

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

23.8

24.0

24.1

24.5

24.7

24.8

25.1

25.3

25.8

25.7

26.4

26.1

 

K.W

3.95

3.89

3.84

3.80

4.00

3.94

3.88

3.85

4.03

3.98

3.92

3.88

 

T.C.

32.8

30.4

27.4

25.5

33.0

30.3

27.6

25.4

33.6

30.5

28.3

25.7

125

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

23.1

23.5

23.4

24.2

23.9

24.1

24.5

24.6

25.3

24.9

26.0

25.2

 

K.W

4.36

4.29

4.24

4.20

4.41

4.34

4.27

4.25

4.43

4.38

4.31

4.27

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.

Multipliers for determining the performance with other indoor sections.

Air Handler

Coil

T.C.

S.C.

KW

N1AHB12

G2FD036(S,H)17

1.02

1.02

1.00

N1AHB12

G2FD046(S,H)17

1.03

1.03

1.01

N1AHD14

G2FD048(S,H)24

1.08

0.91

0.99

N1AHD14

G2FD060(S,H)24

1.09

0.93

0.99

N1VSB12

G2FD036(S,H)17

1.01

1.03

0.92

F2RP/FP036

 

1.03

1.04

0.99

N1VSC16

G3FD048S21

1.08

1.09

0.95

F2RP/FP042

 

1.03

1.05

0.99

F2FP045

 

1.08

1.09

0.97

F2FP048

 

1.05

1.06

0.97

F2RC/FC036

 

1.01

1.03

1.00

 

G1FA048S24

1.06

1.06

1.01

 

G1HD036

1.00

1.00

1.00

 

G1HD048

1.07

1.07

1.06

 

G1NA036S17J

1.01

1.01

0.99

 

G1NA048S21D

1.05

1.05

1.01

 

G1UA036S17,21

1.00

1.00

1.00

 

G1FA048S21

1.06

1.06

1.01

 

G1UA048S17

1.06

1.06

1.02

 

G1UA048S21

1.06

1.06

1.01

 

G2FD035(S,H)14

1.00

1.00

1.00

 

G2FD036(S,H)17

1.02

1.02

1.00

 

G2FD036(S,H)21

1.03

1.03

1.01

 

G2FD042(S,H)21

1.03

1.03

1.01

 

G2FD046(S,H)17

1.03

1.03

1.01

 

G2FD048(S,H)21,24

1.07

1.07

1.01

 

G1FA048S17

1.06

1.06

1.02

Variable Speed

Coil

T.C.

S.C.

KW

Furnace

 

 

 

 

P1DUB16V

G1FA036S17

1.02

1.02

0.95

P1DUB16V

G1FA048S17

1.08

1.08

0.96

P1DUB16V

G1HD036

1.02

1.02

0.96

P1DUB16V

G1HD048

1.09

1.09

1.02

P1DUB16V

G1UA036S17

1.02

1.02

0.95

P1DUB16V

G1UA048S17

1.08

1.08

0.96

P1DUB16V

G2FD036(S,H)17

1.03

1.03

0.95

P1DUB16V

G2FD046(S,H)17

1.05

1.05

0.96

P1DUC20V

G1FA036S21

1.02

1.02

0.95

P1DUC20V

G1FA048S21

1.08

1.08

0.94

P1DUC20V

G1HD036

1.02

1.02

0.93

P1DUC20V

G1HD048

1.11

1.11

0.99

P1DUC20V

G1UA036S21

1.02

1.02

0.95

P1DUC20V

G1UA048S21

1.08

1.08

0.94

P1DUC20V

G2FD036(S,H)21

1.04

1.04

0.92

P1DUC20V

G2FD042(S,H)21

1.05

1.05

0.95

P1DUC20V

G2FD048(S,H)21

1.09

1.09

0.95

P1XDB12V

G2FD036(S,H)17

1.02

1.02

0.97

P1XUB12V

G1FA036S17

1.01

1.01

0.97

P1XUB12V

G1FA048S17

1.08

1.08

0.95

P1XUB12V

G1UA036S17

1.01

1.01

0.97

P1XUB12V

G1UA048S17

1.08

1.08

0.95

P1XUB12V

G2FD036(S,H)17

1.02

1.02

0.97

P1XUB12V

G2FD046(S,H)17

1.05

1.05

0.96

P1XUC20V

G1FA036S21

1.02

1.02

0.95

P1XUC20V

G1FA048S21

1.08

1.08

0.94

P1XUC20V

G1UA036S21

1.02

1.02

0.95

P1XUC20V

G1UA048S21

1.08

1.08

0.94

P1XUC20V

G2FD036(S,H)21

1.04

1.04

0.92

P1XUC20V

G2FD042(S,H)21

1.05

1.05

0.93

Unitary Products Group

15

Page 15
Image 15
York H4DH018 THRU 060 warranty Cooling Performance Data, Air Conditioner Model No