COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

H4DH030S06

 

 

 

 

 

 

 

 

 

 

INDOOR COIL MODEL NO.

 

G1FA036S17,21

 

 

 

 

 

 

 

 

 

CONDENSER

ID CFM

 

980

 

 

 

1030

 

 

1080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENTERING AIR

ID DB

85

80

 

75

70

85

80

75

70

85

80

75

70

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ID WB

72

67

 

62

57

72

67

62

57

72

67

62

57

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

35.3

32.6

 

29.8

27.3

35.7

32.9

30.1

27.8

35.9

33.2

30.4

28.1

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

22.6

22.7

 

23.1

23.1

23.7

23.8

24.1

24.5

24.7

24.8

25.2

25.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W

2.35

2.32

 

2.30

2.28

2.39

2.37

2.35

2.33

2.43

2.40

2.38

2.37

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

33.7

31.2

 

28.5

26.1

34.0

31.4

28.8

26.6

34.3

31.7

29.1

26.9

85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

22.0

22.2

 

22.4

22.6

23.1

23.2

23.5

23.8

24.1

24.3

24.6

24.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W

2.62

2.59

 

2.55

2.52

2.67

2.63

2.60

2.57

2.70

2.67

2.64

2.61

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

32.6

30.1

 

27.6

25.4

32.9

30.4

27.9

25.8

33.0

30.6

28.3

26.1

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

21.6

21.7

 

22.0

22.4

22.7

22.8

23.1

23.4

23.7

23.8

24.5

24.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W

2.90

2.85

 

2.81

2.78

2.94

2.90

2.86

2.82

2.98

2.94

2.90

2.86

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

31.4

29.0

 

26.6

24.6

31.6

29.3

26.9

24.9

31.8

29.5

27.3

25.1

105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

21.1

21.3

 

21.6

21.9

22.2

22.4

22.7

23.0

23.3

23.5

24.0

23.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W

3.18

3.13

 

3.09

3.06

3.22

3.18

3.14

3.10

3.26

3.22

3.18

3.14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

30.1

27.9

 

25.6

23.7

30.2

28.1

26.0

23.9

30.4

28.2

26.2

24.6

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

20.8

20.8

 

21.2

21.4

21.7

21.9

22.5

22.4

22.9

22.9

23.4

23.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W

3.47

3.44

 

3.41

3.38

3.52

3.49

3.46

3.43

3.56

3.53

3.50

3.47

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

28.8

26.8

 

24.6

22.8

28.8

26.9

25.1

22.9

29.0

26.9

25.1

24.1

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

20.5

20.3

 

20.8

20.9

21.2

21.4

22.3

21.8

22.5

22.3

22.8

23.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W

3.76

3.75

 

3.73

3.70

3.82

3.80

3.78

3.76

3.86

3.84

3.82

3.80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.

Multipliers for determining the performance with other indoor sections.

Air Handler

Coil

T.C.

S.C.

KW

 

 

 

 

 

N1AHB12

G2FD030(S,H)17

0.97

0.97

0.96

 

 

 

 

 

N1AHB12

G2FD036(S,H)17

0.99

0.99

0.97

 

 

 

 

 

N1VSB12

G2FD036(S,H)17

1.02

1.02

0.98

 

 

 

 

 

N1VSB12

G2FD046(S,H)17

1.05

1.05

1.00

 

 

 

 

 

F2RC/FC030

 

0.93

0.93

0.93

 

 

 

 

 

F2RP/FP030

 

0.99

0.99

0.98

 

 

 

 

 

F2FP040

 

1.03

1.03

1.00

 

 

 

 

 

F2RP/FP036

 

1.02

1.02

1.00

 

 

 

 

 

 

G1HD036

0.99

0.99

0.98

 

 

 

 

 

 

G1NA030S17

0.97

0.97

0.96

 

 

 

 

 

 

G1UA030S14

0.95

0.95

0.96

 

 

 

 

 

 

G1UA036S17,21

1.00

1.00

1.00

 

 

 

 

 

 

G1FA048S21

1.03

1.04

1.00

 

 

 

 

 

 

G1UA048S17

1.03

1.03

1.00

 

 

 

 

 

 

G1UA048S21

1.03

1.03

1.00

 

 

 

 

 

 

G2FD030(S,H)17

0.97

0.97

0.96

 

 

 

 

 

 

G2FD035(S,H)14

0.99

0.99

0.99

 

 

 

 

 

 

G2FD036(S,H)17

0.99

0.99

0.97

 

 

 

 

 

 

G2FD036(S,H)21

0.99

0.99

0.97

 

 

 

 

 

 

G2FD048(S,H)21,24

1.02

1.02

1.00

 

 

 

 

 

 

G1FA030S14

0.95

0.95

0.96

 

 

 

 

 

 

G1FA048S17

1.03

1.03

1.00

 

 

 

 

 

Variable Speed

Coil

T.C.

S.C.

KW

Furnace

 

 

 

 

P1DUB16V

G1UA036S17

1.02

1.02

0.94

P1DUB16V

G1UA048S17

1.06

1.06

0.93

P1DUB16V

G2FD030(S,H)17

1.02

1.02

0.94

P1DUB16V

G2FD036(S,H)17

1.01

1.01

0.89

P1XDB12V

G2FD036(S,H)17

0.97

0.97

0.92

P1XUB12V

G1FA036S17

1.02

1.02

0.93

P1XUB12V

G1FA048S17

1.06

1.06

0.95

P1XUB12V

G1UA036S17

1.02

1.02

0.93

P1XUB12V

G1UA048S17

1.06

1.06

0.95

P1XUB12V

G2FD030(S,H)17

1.01

1.01

0.95

P1XUB12V

G2FD036(S,H)17

1.01

1.01

0.90

P1XUC16V

G1FA036S21

1.02

1.02

0.93

P1XUC16V

G1FA048S21

1.06

1.06

0.95

P1XUC16V

G1UA036S21

1.02

1.02

0.93

P1XUC16V

G1UA048S21

1.06

1.06

0.95

P1XUC16V

G2FD036(S,H)21

0.99

0.99

0.89

P1DUA12V

G1FA030S14

0.97

0.97

0.92

P1DUA12V

G1FA036S14

1.01

1.01

0.95

P1DUA12V

G1HD036

1.00

1.00

0.93

P1DUA12V

G1UA030S14

0.97

0.97

0.92

P1DUA12V

G1UA036S14

1.01

1.01

0.95

P1DUB16V

G1FA036S17

1.02

1.02

0.94

P1DUB16V

G1FA048S17

1.06

1.06

0.93

P1DUB16V

G1HD036

1.01

1.01

0.90

P1XUC16V

G2FD048(S,H)21

1.04

1.04

0.94