York H4DH018 THRU 060 warranty Physical and Electrical Data, Model

Models: H4DH018 THRU 060

1 20
Download 20 pages 49.34 Kb
Page 2
Image 2
Physical and Electrical Data

036-21020-003 Rev. C (0203)

Physical and Electrical Data

MODEL

 

 

H4DH018S06

H4DH024S06

H4DH030S06

H4DH036S06

H4DH042S06

H4DH048S06

H4DH060S06

Unit Supply Voltage

 

 

 

 

208/230 – 1 – 60

 

 

 

Normal Voltage Range 1

 

 

 

187 to 252

 

 

 

Minimum Circuit Ampacity

10.1

12.1

18.5

22.0

 

25.2

31.6

37.4

Max. Overcurrent Device Amps 2

15

20

30

35

 

40

50

55

Compressor Type 3

 

Recip

Inertia

ScrollB

ScrollB

 

ScrollB

ScrollB

ScrollC

Compressor Amps

Rated Load

7.7

9.3

14.1

16.6

 

19.2

24.3

28.8

Locked Rotor

48

57

78

98

 

105

150

169

Crankcase Heater

 

No

Yes

No

No

 

No

No

No

Fan Motor Amps

Rated Load

0.5

0.5

0.9

1.2

 

1.2

1.2

1.4

Fan Diameter Inches

 

18

18

18

24

 

24

24

24

 

 

 

Rated HP

1/12

1/12

1/8

1/4

 

1/4

1/4

1/3

Fan Motor

 

Nominal RPM

1100

1100

1075

850

 

850

850

1100

 

 

 

Nominal CFM

1500

1500

2050

3100

 

3100

3100

4100

 

 

Face Area Sq. Ft.

14.1

14.1

14.1

20

 

20

24

24

Coil

 

Rows Deep

1

1

1

1

 

1

1

1

 

 

Fin / Inches

20

20

20

18

 

18

20

20

Liquid Line

OD

 

3/8

3/8

3/8

3/8

 

3/8

3/8

3/8

Vapor Line OD

 

5/8

3/4

3/4

3/4

 

7/8

7/8

7/8

Unit Charge (Lbs. - Oz.) 4

4 - 14

5 - 1

5 - 4

5 - 15

 

6 - 12

8 - 10

7 - 13

Charge Per Foot, Oz.

0.68

0.68

0.68

0.68

 

0.70

0.70

0.70

Operating Weight Lbs.

144

154

148

225

 

230

235

243

1.Rated in accordance with ARI Standard 110, utilization range “A”.

2.Dual element fuses or HACR circuit breaker.

3.All scrolls listed with a superscript “B” are Bristol scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.

4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot valve.

48" OVERHEAD CLEARANCE

C

B

MODEL AIR IN 4 SIDES

A

 

5-1/2

VAPOR

 

CONNECTION

2-3/8

 

LIQUID CONNECTION

 

 

3-1/8

All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.

UNIT

DIMENSIONS

 

REFRIGERANT

MODEL

 

CONNECTION

 

(INCHES)

 

HDH

 

 

LINE SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

C

Liquid

Vapor

 

 

 

 

 

 

 

 

018

30-1/8

24

 

24

 

 

5/8

 

 

 

 

 

 

 

 

024

30-1/8

24

 

24

 

 

 

 

 

 

 

 

 

 

3/4

030

30-1/8

24

 

24

 

 

 

 

 

 

 

3/8

 

 

036

31-7/8

35

 

35

 

 

 

 

 

 

 

 

 

 

042

31-7/8

35

 

35

 

 

 

 

 

 

 

 

 

 

7/8

048

37-7/8

35

 

35

 

 

 

 

 

 

 

 

 

 

060

37-7/8

35

 

35

 

 

 

 

 

 

 

 

 

 

 

2

Unitary Products Group

Page 2
Image 2
York H4DH018 THRU 060 warranty Physical and Electrical Data, Model