York WR240, WR300 YTG-B-0107, SOUND POWER RATING1, Capacity Ratings - Ari, Gas Heat Ratings

Models: WR240 WR300

1 56
Download 56 pages 45.29 Kb
Page 11
Image 11
TABLE 1: SOUND POWER RATING1

262292-YTG-B-0107

TABLE 1: SOUND POWER RATING1

 

 

ESP

BLOWER

 

 

 

 

SOUND POWER (db 10-12

Watts)

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

Octave Band Centerline Frequency (Hz)

 

SWL

dB(A)

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

@

 

 

IWG

RPM

BHP

63

125

 

250

500

1,000

2,000

 

4,000

8,000

dB(A)

 

 

 

 

10Ft.2

 

 

 

 

 

WR180

6,000

1.00

1,080

4.60

99

99

 

89

82

84

77

 

72

67

89

56

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WR240

8,000

1.00

1,120

6.65

102

102

 

92

85

87

80

 

75

70

92

59

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WR300

10,000

1.30

1160

12.5

108

108

 

98

91

93

86

 

81

76

98

65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.

2.At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 360)1

MODEL

MBH

EER2

IPLV3

COOLING ONLY

 

 

 

WR180C/E00

180

11.9

12.7

WR240C/E00

240

11.0

11.3

WR300C/E00

300

10.0

10.6

COOLING WITH GAS HEAT

 

 

 

WR180N/S

180

11.9

12.7

WR240N/S

240

11.0

11.3

WR300N/S

300

10.0

10.6

COOLING WITH ELECTRIC HEAT

 

 

WR180E18

180

11.9

12.7

WR180E36

180

11.9

12.7

WR180E54

178

11.7

12.5

WR180E72

178

11.7

12.5

WR240E18

240

11.0

11.3

WR240E36

240

11.0

11.3

WR240E54

238

10.8

11.1

WR240E72

238

10.8

11.1

WR300E18

300

10.0

10.6

WR300E36

300

10.0

10.6

WR300E54

298

9.8

10.4

WR300E72

298

9.8

10.4

1.Certified in accordance with the Unitary Large Equipment certification program which is based on ARI Standard 340/ 360.

2.EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt).

3.IPLV = Integrated Part Load Value.

TABLE 3: GAS HEAT RATINGS

MODEL

MBH INPUT

MBH OUTPUT

WR180N/S24

300

240

 

 

 

WR180N/S32

400

320

WR240N/S24

300

240

 

 

 

WR240N/S32

400

320

WR300N/S24

300

240

 

 

 

WR300N/S32

400

320

NOTE:All gas units are two-stage heating. First stage is 50% of total.

S.S.E. = Steady State Efficiency (80%) - output divided by input.

For units with VFD and electric or gas heat, the speed of the indoor blower motor continues to be controlled by duct static pressure via the VAV control board.

If there are VAV boxes present in the duct sys- tem, the boxes must be driven to the full-open position using a customer-supplied power source to assure adequate airflow across elec- tric heating elements or gas heat exchanger tubes.

Unitary Products Group

11

Page 11
Image 11
York WR240, WR300 warranty YTG-B-0107, SOUND POWER RATING1, Capacity Ratings - Ari, Gas Heat Ratings, Unitary Products Group

FAQ

What is the sound power rating for York air conditioners?

The sound power ratings are provided for reference only as the actual dBA values can vary based on system design and fan manufacture.

What is EER and IPLV in capacity ratings?

EER is the Energy Efficiency Ratio at full load, while IPLV stands for Integrated Part Load Value for air conditioners.

How is the steady state efficiency calculated for gas units?

The steady state efficiency is calculated as the output divided by the input, and it stands at 80% for the gas units.