York WR300, WR240 warranty Minimum Clearances

Models: WR240 WR300

1 56
Download 56 pages 45.29 Kb
Page 48
Image 48
TABLE 35: MINIMUM CLEARANCES

262292-YTG-B-0107

TABLE 35: MINIMUM CLEARANCES

LOCATION

CLEARANCE

Front

36”

Rear

24” (Less Economizer)

49” (With Economizer)

 

 

 

Left Side (Filter Access)

24” (Less Economizer)

36” (With Economizer)3

Right Side (Cond. Coil)

36”

Below Unit1

0”

Above Unit2

72” With 36” Maximum

Horizontal Overhang (For

 

Condenser Air Discharge)

 

 

1.Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.

2.Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.

3.If economizer is factory installed, the unassembled rain hood must be removed from its ride along position in front of evapora- tor coil, or in the outdoor air compartment, prior to final installa- tion.

 

 

ECONOMIZER

 

 

MOTORIZED

SUPPLY AIR

POWER EXHAUST

DAMPER

RAIN HOOD

RAIN HOOD

COMPARTMENT

(on Return Air Compartment)

(on Outdoor Air Compartment)

 

NOTE: ELEC / ELEC Models: Units and ductwork are approved

for zero clearance to combustible material when equipped with electric heaters.

GAS / ELEC Models: A 1” clearance must be provided between any combustible material and the supply air ductwork for a distance of 3 feet from the unit.

The products of combustion must not be allowed to accumulate within a confined space and recirculate.

Locate unit so that the vent air outlet hood is at least:

Three (3) feet above any force air inlet located within 10 horizontal feet (excluding those integral to the unit).

Four (4) feet below, four horizontal feet from, or one foot above any door or gravity air inlet into the building.

Four (4) feet from electric and gas meters, regulators and relief equipment.

ECONOMIZER / MOTORIZED DAMPER

AND POWER EXHAUST RAIN HOODS

FIXED

OUTDOOR AIR INTAKE HOOD (located on Return Air Compartment)

36-5/8”

Manual background16-1/8” Manual background

5”

28-3/16”92”

1“ CONDENSATE DRAIN

(Must be trapped)

REAR VIEW

LH VIEW

DETAIL “Y”

UNIT WITH RAIN HOODS

FIGURE 14:UNIT DIMENSIONS WR180, 240 & 300 (RAINHOOD)

48

Unitary Products Group

Page 48
Image 48
York WR300, WR240 warranty Minimum Clearances

FAQ

What are the minimum clearances required for York air conditioners WR300 and WR240?

The minimum clearances for these air conditioners are listed in Table 35, which includes front, rear, left side filter access, and other necessary clearances for safe installation.

Can York air conditioners WR300 and WR240 be installed indoors?

No, these units must be installed outdoors to ensure proper ventilation and safety. Overhanging structures or shrubs should not obstruct the condenser air discharge outlet.

Are there specific requirements for installing electric or gas models of York air conditioners WR300 and WR240?

Yes, specific clearances and ventilation requirements must be followed when installing electric or gas models of these air conditioners to prevent the accumulation of products of combustion within a confined space.