York WR300, WR240 warranty Four And Six Point Loads

Models: WR240 WR300

1 56
Download 56 pages 45.29 Kb
Page 50
Image 50
FIGURE 17:FOUR AND SIX POINT LOADS

262292-YTG-B-0107

 

 

B

 

 

 

E

 

 

 

 

 

 

F

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

A

 

 

 

A

 

 

 

 

D

 

 

 

B

 

 

 

 

 

 

 

 

 

FIGURE 17:FOUR AND SIX POINT LOADS

 

 

 

 

 

TABLE 36: FOUR AND SIX POINT LOADS

 

 

 

 

 

Unit Size

Operating

 

4 Point Loads (lbs)

 

 

 

Weight

A

B

C

D

 

 

 

 

 

WR180 Gas

2900

495

924

965

516

 

 

WR240 Gas

3200

558

1042

1042

558

 

 

WR300 Gas

3300

575

1075

1075

575

 

 

WR180 Elec

2700

460

860

898

481

 

 

WR240 Elec

3000

523

977

977

523

 

 

WR300 Elec

3100

540

1010

1010

540

 

 

Unit Size

Operating

 

 

6 Point Loads (lbs)

 

 

Weight

A

B

C

D

E

F

 

WR180 Gas

2900

330

344

494

643

616

473

WR240 Gas

3200

372

372

533

695

695

533

WR300 Gas

3300

383

383

550

717

717

550

WR180 Elec

2700

307

321

460

599

573

440

WR240 Elec

3000

349

349

500

651

651

500

WR300 Elec

3100

360

360

517

673

673

517

50

Unitary Products Group

Page 50
Image 50
York WR300, WR240 warranty Four And Six Point Loads

FAQ

What is included in the table?

The table includes operating weights and loads for different unit sizes and types of York air conditioners.

What are the load values for WR240 Gas unit?

The 4 point load values for WR240 Gas unit are 558, 1042, 1042, 558 lbs.

What are the load values for WR300 Electric unit?

The 6 point load values for WR300 Electric unit are 360, 360, 517, 673, 673, 517 lbs.