TABLE 6: COOLING CAPACITIES FOR WR300 (CONTINUED)
Air on Evaporator Coil |
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
| |||||||
|
|
| 115°F |
|
|
|
|
|
| 125°F |
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| WB | Total | Total2 |
| Sensible Capacity (MBH)* |
| Total | Total2 |
| Sensible Capacity (MBH)* |
| |||||||
CFM | Cap.1 | Input |
| Return Dry Bulb (°F) |
| Cap.1 | Input |
| Return Dry Bulb (°F) |
| ||||||||
| (°F) | (MBH) | (kW) |
|
|
|
|
|
| (MBH) | (kW) |
|
|
|
|
|
| |
| 90 | 85 | 80 | 75 | 70 | 65 | 90 | 85 | 80 | 75 | 70 | 65 | ||||||
|
| |||||||||||||||||
| 77 | 281 | 26.6 | 128 | 108 | 84 | 60 | 36 | 12 | 265 | 28.8 | 122 | 99 | 75 | 51 | 27 | - | |
6250 | 72 | 262 | 26.0 | 172 | 148 | 124 | 100 | 76 | 52 | 248 | 28.2 | 165 | 141 | 117 | 93 | 69 | 45 | |
67 | 243 | 25.3 | 216 | 188 | 164 | 140 | 116 | 92 | 230 | 27.5 | 207 | 183 | 159 | 135 | 111 | 87 | ||
| ||||||||||||||||||
| 62 | 220 | 24.8 | 218 | 209 | 185 | 161 | 137 | 113 | 208 | 26.9 | 207 | 193 | 170 | 146 | 122 | 98 | |
| 77 | 324 | 30.9 | 155 | 127 | 98 | 70 | 41 | 12 | 305 | 33.5 | 149 | 116 | 88 | 59 | 31 | - | |
7500 | 72 | 302 | 30.2 | 203 | 174 | 146 | 117 | 88 | 60 | 285 | 32.8 | 194 | 166 | 137 | 109 | 80 | 52 | |
67 | 280 | 29.4 | 250 | 222 | 193 | 164 | 136 | 107 | 265 | 32.0 | 239 | 215 | 186 | 158 | 129 | 101 | ||
| 62 | 254 | 28.8 | 252 | 245 | 217 | 188 | 159 | 131 | 239 | 31.3 | 239 | 228 | 199 | 171 | 142 | 114 | |
| 57 | 252 | 28.4 | 252 | 252 | 241 | 213 | 184 | 155 | 239 | 30.9 | 239 | 239 | 227 | 198 | 170 | 141 | |
| 77 | 324 | 31.1 | 162 | 129 | 100 | 70 | 41 | 11 | 304 | 33.7 | 157 | 118 | 89 | 60 | 31 | - | |
7750 | 72 | 302 | 30.4 | 207 | 177 | 148 | 118 | 89 | 60 | 284 | 33.0 | 198 | 168 | 139 | 110 | 80 | 51 | |
67 | 280 | 29.6 | 251 | 225 | 196 | 166 | 137 | 108 | 264 | 32.3 | 238 | 218 | 189 | 160 | 130 | 101 | ||
| 62 | 254 | 29.0 | 252 | 249 | 220 | 190 | 161 | 132 | 239 | 31.6 | 238 | 233 | 202 | 173 | 143 | 114 | |
| 57 | 252 | 28.5 | 252 | 252 | 245 | 215 | 186 | 157 | 238 | 31.1 | 238 | 238 | 230 | 201 | 171 | 142 | |
| 77 | 323 | 31.3 | 168 | 131 | 101 | 71 | 41 | 11 | 303 | 34.0 | 164 | 120 | 90 | 60 | 30 | - | |
8000 | 72 | 302 | 30.5 | 210 | 180 | 150 | 120 | 89 | 59 | 284 | 33.2 | 201 | 171 | 141 | 111 | 81 | 51 | |
67 | 280 | 29.8 | 252 | 229 | 199 | 168 | 138 | 108 | 264 | 32.5 | 238 | 222 | 191 | 161 | 131 | 101 | ||
| 62 | 253 | 29.2 | 252 | 252 | 223 | 193 | 163 | 132 | 238 | 31.8 | 238 | 238 | 205 | 175 | 145 | 115 | |
| 57 | 252 | 28.7 | 252 | 252 | 248 | 218 | 188 | 158 | 238 | 31.4 | 238 | 238 | 233 | 203 | 173 | 143 | |
| 72 | 303 | 30.5 | 218 | 187 | 156 | 125 | 93 | 62 | 284 | 33.1 | 209 | 178 | 147 | 116 | 85 | 53 | |
8650 | 67 | 281 | 29.8 | 253 | 238 | 206 | 175 | 144 | 113 | 265 | 32.4 | 239 | 231 | 200 | 168 | 137 | 106 | |
62 | 254 | 29.2 | 253 | 253 | 232 | 201 | 169 | 138 | 239 | 31.7 | 239 | 239 | 214 | 182 | 151 | 120 | ||
| ||||||||||||||||||
| 57 | 253 | 28.7 | 253 | 253 | 251 | 220 | 189 | 157 | 239 | 31.3 | 239 | 239 | 236 | 205 | 174 | 143 | |
| 72 | 304 | 30.5 | 226 | 194 | 162 | 129 | 97 | 65 | 285 | 33.0 | 218 | 185 | 153 | 121 | 89 | 56 | |
9300 | 67 | 282 | 29.8 | 254 | 247 | 214 | 182 | 150 | 117 | 265 | 32.3 | 239 | 239 | 208 | 176 | 143 | 111 | |
62 | 255 | 29.1 | 254 | 254 | 241 | 208 | 176 | 144 | 240 | 31.6 | 239 | 239 | 222 | 190 | 158 | 126 | ||
| ||||||||||||||||||
| 57 | 254 | 28.7 | 254 | 254 | 254 | 221 | 189 | 157 | 239 | 31.2 | 239 | 239 | 239 | 207 | 175 | 143 |
1.The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
All Sensible Capacity
Unitary Products Group | 17 |